ATC-300/900 Breaker Based Transfer Switch
Figure 39. Horizontal Power Panel
Step 3:
Turn the generator OFF at the generator control panel.
This will prevent unexpected activation of the generator.
Step 4:
Connect the Engine Generator Start wires as shown in
Section 4.7. This contact is CLOSED whenever the
engine generator is needed, and should be connected to a
generator controller.
NEVER
connect directly to a starter
solenoid or ignition system. See the Genset manufacturer
instruction leaflet for recommended wire sizes and loca-
tion procedures.
Step 5:
Apply Utility (Source 1) power. If the switch is properly
applied for the system voltage ordered, the display should
work and the Source 1 Available white LED should light
(Figure 40). Using a voltmeter, check for proper system
voltage on Source 1 and load terminals. Check all phases
on a 3-phase switch. Voltage measurements should be
taken phase to phase and phase to neutral.
Figure 40. ATC-300+Controller (Utility Supplying Load)
Step 6:
To view the setpoints, press the
<Step/Enter>
pushbut-
ton and enter the Password.
Note:
The factory default Password is 0300. Once all installation and test-
ing is complete, the Password should be changed by authorized per-
sonnel to a unique Password for the equipment.
After entering the password, press the
<Step/Enter>
pushbutton until the VIEW SETPOINTS menu appears.
Select YES. Press the
<Step/Enter>
pushbutton to
scroll through the setpoints (Figures 41 through 42 and
the controller's instruction booklet).