ATC-300 /900 Breaker Based Transfer Switch
Figure 4. Typical Power Panel for 30-150 A Models (Deadfront
Cover Installed).
Molded case switches and the associated transfer mechanisms
are mounted vertically to save space in the assembly. The com-
pact, vertical configuration uses a positive, metallic transfer and
interlocking system between the molded case switches.
The Eaton ATS was designed with easy installation and simplified
maintenance in mind. Three main panels compromise the transfer
switch design:
1. Power panel;
2. Voltage selection and transformer panel (if required); and
3. Controller.
Figure 5. Vertical Design Transfer Switch with the Deadfront
Cover in Place Over the Power Panel (225-1200 A).
Each panel is independently mounted with interconnecting wiring
terminated at the connector receptacles on the ATC-300 Control-
ler. Door or individual panel removal is achieved without disturb-
ing critical connections by removing the connectors from the
receptacles and cutting the wire ties that secure the wires to the
door.
Mounting the enclosure is simple using top and bottom mounting
flanges with elongated (teardrop) mounting holes. These mount-
ing holes, along with power panel positioning bolts and pre-tapped
inserts, insure proper power panel mounting after the initial enclo-
sure installation or when switching from top to bottom or bottom
to top entry. Refer to Section 4 for specific mounting and modifi-
cation details.
Table 1. Withstand Ratings
UL 1008 WITHSTAND AND CLOSE-ON RATINGS (kA)
Switch
Rating
Amperes
UL 1008 3-Cycle
“Any Breaker” Rating
Rating When Used
With Upstream Fuse
240 Vac 480 Vac
600 Vac
Maximum
Fuse Rating
Fuse
Type
600 Vac
30-100
150
150-225
225
100
100
100
100
65
65
65 (240 Vac)
65
25
25
25
25
200
400
400
400
J, T
J, T
J, T
J, T
200
200
200
200
300
400
600
100
100
100
65
65
65
25
25
25
400
600
1200
J, T
J, T
J, T
200
200
200
800
1000
65
65
50
50
25
25
1600
1600
L
L
200
200
4 pole 480 Vac are rated 35 kA