background image

I.B. 48003

Page 19

Effective 11/97

If for some reason a coil must be changed, proceed as
follows:

1.

Deenergize all circuits.

2.

Loosen the set screw holding the kickout spring
adjusting screw.  See Figure 6.

Loosen the kickout spring adjusting screw until the
kickout spring can be removed easily.

NOTE:  Whenever adjusting the kickout spring lever,
put a free hand over the kickout spring as a precau-
tion.

3.

Remove leads to coil terminals, noting their position
for later reconnection.

4.

Remove the two 0.313-inch magnet mounting bolts.
Remove the bolts completely and set aside until later.

5.

Lift magnet and coil upward and out.

6.

Remove the coil clip from old coil and install on the
new coil.  Note that the coil clip is THREADED.
Remove the coil lock nut before removing the screw.
When installing the clip on the new coil, tighten the
screw only to snug.  Then lock the screw into the coil
clip with the lock nut.  Note that the head of the screw
must be toward the armature.

7.

Re-install the magnet into the coil, and lower both
into position.  Do not force.  Sometimes it is neces-
sary to jiggle the coil slightly into its sealed position.

8.

Install the two magnet mounting bolts, but do not
tighten.

9.

Re-connect the coil circuit.

10. After checking for safe operation, energize the coil

and close the contactor.  While the magnet is sealed,
tighten the two magnet mounting bolts, using continu-
ing care against shock.  Then de-energize the coil.

11. Re-install the kickout spring, making sure to put the

two ends of the spring wire downward, so that the
spring will take a natural bow.  Tighten the adjusting
screw until the kickout spring lever is approximately
vertical, and the armature is solidly against its stop
on the molded frame.  See Figure 12.  When a
screwdriver is pushed against the bottom end of the
armature in the open position, the armature must not
move.  If it does, the kickout spring should be tight-
ened further to push the armature to a solid position.
Tighten the set screw to lock the kickout spring
adjusting screw.

If the magnet chatters, look for mechanical interference
that prevents the magnet from sealing.  If there is no
interference, then the magnet itself may be misaligned.
The magnet gap can be seen from the left and the right
sides with the help of a flashlight.  The stationary magnet
can be aligned with a 0.50-inch (12.7mm) diameter steel
rod inserted into the two holes in the core of the magnet

and used as a lever to put a corrective set into the
magnet frame.  it should not be necessary to do this
unless the contactor has been damaged and it can be
seen that the armature does not fit against the magnet.
A poor magnet-to-armature fit usually produces a high
dropout voltage and/or chatter.

Mechanical interference can be produced by various
incorrect adjustments.  Two specific points to check are:

A. Armature travel incorrect, causing the contact springs

to be compressed into a solid, non-resilient “tube”
that stops the crossbar rigidly.  Call Cutler-Hammer
Service for assistance.

B. The auxiliary contact assemblies operating arms are

misadjusted, so that a contact plunger bottoms
solidly before the magnet seals.  When the contactor
is fully sealed closed, there should still be a small
amount of travel remaining for these plungers.  Adjust
as described below.

Contactor Auxiliary Contacts

Two Type L64 auxiliary contact assemblies are mounted
on the contactor front (right side) to provide four isolated
auxiliary, 600 VAC, 10 ampere, double-break contacts for
use in control circuits.  Any combination of normally-open
or normally-closed circuits is available by selection of the
appropriate assembly from Table IV.

The normally-open (NO) L64 auxiliary contacts close just
after the main contacts of the contactor close.  The
normally-closed (NC) L64 auxiliary contacts open just
before the main contacts close.

In addition, a single-circuit Type L63 auxiliary contact
(normally-closed) is mounted on the front (left side) and
is connected to coil terminals C and D.  This auxiliary
contact (578D461G03) is equipped with permanent
magnet blowouts on the contacts.

TABLE IV. TYPE L64 AUXILIARY CONTACTS

Circuit Combination Provided

 Part Number

By One Auxiliary Contact

Assembly

843D943G21

One Normally-Open and
One Normally-Closed

843D943G22

Two Normally-Open

843D943G23

Two Normally-Closed

Summary of Contents for Cutler-Hammer Ampgard SC9000

Page 1: ...shown in Table I The controller may also be used to switch transformer windings or capacitor banks Each Ampgard controller occupies all or a portion of a steel structure that may also enclose a horizontal bus system to distribute power to two or more sections and a vertical bus system in each section con nected to the horizontal main bus system The controllers are configured for full voltage or re...

Page 2: ...ch See Figure 2 Connect the conductors from the motor to these latter terminals LOW VOLTAGE CONTROL COMPONENTS The low voltage components consisting of an interposing relay protective relays and optional equipment are generally mounted on a slide out panel The single phase control power transformer is bolted to the contactor frame The capacity of this transformer ranges from 600 VA to 2 kVA depend...

Page 3: ...I B 48003 Page 3 Effective 11 97 Fig 4 Ampgard Components Two Starters Controllers Shown ...

Page 4: ... mounted between phases and also between the two outside poles and the isolating switch end plates This isolating switch is a nonload break device It must never close or interrupt a power load However it does have a limited capacity for interrupting the single phase control power and potential transformers exciting current In terms of transformer ratings the maximum load is the equivalent of an un...

Page 5: ...tor is 7600 amperes r m s symetrical The current transform ers overload protector and power circuit fuses are coordinated with the motor characteristics so that the controller must be used with the motor for which it was designed Motors with special characteristics often require additional protective relays Consult the instruc tion leaflet for that particular protective relay before attempting any...

Page 6: ...witch Interlock There is also a mechanical interlock that is designed to prevent the isolating switch from closing with the contactor already closed and to prevent the contactor from closing while the isolating switch is being opened This latter state the transition phase is shown in Figure 7 With the isolating switch fully open or fully closed the contactor may be opened or closed See Figure 8 If...

Page 7: ...for each pole of the contactor A three pole contactor has three vacuum bottles A metal bellows like a small circular accordion allows the moving contact to be closed and pulled open from the outside without letting air into the vacuum chamber of the bottle Both the bellows and the metal to ceramic seals of modern bottles have been improved to the point that loss of vacuum is no longer cause for un...

Page 8: ... fuses are mounted directly above the contactor as for example in the case of one contactor in a reversing controller no barriers are required or furnished CONTACTOR MOUNTED COMPONENTS To simplify installation and servicing a number of related components are mounted on the Type SJS contactor chassis a control power transformer with test plug and fuses instrument quality potential transformers with...

Page 9: ...I B 48003 Page 9 Effective 11 97 Fig 11 Type SJS Contactor Positions ...

Page 10: ... barriers for easier access To reinstall reverse the procedure INSTALLATION This industrial type control is designed to be installed by adequately trained and qualified personnel with appropri ate supervision These instructions do not cover all details variations or combinations of the equipment its storage delivery installation check out safe operation or maintenance Care must be exercised to com...

Page 11: ...low voltage cables may be conveniently arranged near the right hand enclosure wall See Figure 3 G ISOLATING SWITCH H ISOLATING SWITCH AUXILIARY CONTACT TERMINAL BLOCKS J ISOLATING SWITCH MECHANICAL INTERLOCK K FUSE PULLER L LOAD CABLES M MOTOR TERMINALS A POSITIONING BOLTS B POWER CIRCUIT FUSES C MEDIUM VOLTAGE COMPARTMENT DOOR D CONTROL TERMINAL BLOCKS E VACUUM CONTACTOR F LOW VOLTAGE COMPARTMENT...

Page 12: ...ge door C 3 Separate the contactor side of the control wires from the terminal block D 4 Disconnect the auxiliary contact terminal blocks H on the isolating switch 5 Remove contactor E with a sharp pull forward 6 Part way out the contactor will reach a balanced position Lower the contactor to the floor and slide it out of the way The contactor weighs approximately 160 lbs 73 kilograms If a contact...

Page 13: ... shown 10 Refer to load cable instruction tag located at motor terminals M for load wiring instructions Controller is now ready to wire both line and load 11 After wiring reverse the procedure to reassemble Slide the isolating switch in place and secure with two bolts Refer to Steps 7 and 8 12 Check to make sure each fuse clamp is in correct position in fuse locator Refer to instructions on the lo...

Page 14: ... material 6 THE INSULATION LEVEL OF THE STARTER IS CHECKED AND RECORDED BEFORE THE STARTER IS ENERGIZED See GENERAL MAIN TENANCE 14 Reconnect the clevis attached to the mechanical interlock arm Reconnect the isolating switch auxiliary contact terminal blocks Reconnect the contactor control wire terminal blocks Refer to Steps 3 and 4 15 Install the three power circuit fuses Make sure each fuse is f...

Page 15: ...eres Any spark across the contact gap indicates failure SOME DC HIGH POTENTIAL UNITS OPERATING AS UNFILTERED HALF WAVE RECTIFIERS ARE NOT SUITABLE FOR TESTING VACUUM INTERRUPTERS BECAUSE THE PEAK VOLTAGE APPEARING ACROSS THE INTERRUPTERS CAN BE SUBSTANTIALLY GREATER THAN THE VALUE INDICATED When a vacuum bottle is tested with voltage over 5000 volts across its open gap there is some possibility of...

Page 16: ...practices c Be trained in rendering first aid d Be knowledgeable with respect to electrical installa tion codes and standards for example the National Electrical Code NEC MAINTENANCE PROGRAM A maintenance program should be established as soon as the controller has been installed and put into opera tion After the controller has been inspected a number of times at monthly intervals and the condition...

Page 17: ...same manner and record Investi gate any abrupt reduction in resistance or any unusually low reading Dust and moisture are detrimental to electrical equipment and industrial equipment is designed to tolerate a less than perfect environment However excessive dust can cause trouble and should be wiped or blown off at appro priate intervals If the contactor is wet for any reason dry it until the insul...

Page 18: ... service after a fault However if there is no physical evidence of stress and if the overtravel exceeds the 020 inch 51 mm minimum the bottles can then be dielectrically tested as outlined previously If physical stress overtravel and dielectric test results are within acceptable limits it is reasonable to return the contactor to service after a fault Magnet Operating Range When properly adjusted a...

Page 19: ... for mechanical interference that prevents the magnet from sealing If there is no interference then the magnet itself may be misaligned The magnet gap can be seen from the left and the right sides with the help of a flashlight The stationary magnet can be aligned with a 0 50 inch 12 7mm diameter steel rod inserted into the two holes in the core of the magnet and used as a lever to put a corrective...

Page 20: ...bending the operating arm with the forked end of the bottle wrench See Figure 15 After an L63 auxiliary contact is replaced gap adjustment may be made by first loosening the jam nut on the operating arm with a 0 438 inch open end wrench The gap size is changed by rotating the 0 25 20 bolt Clock wise rotation will increase the gap distance Counter clockwise rotation will decrease the gap distance U...

Page 21: ...I B 48003 Page 21 Effective 11 97 Fig 16 Cable and Connection Diagram ...

Page 22: ... It is designed to hold the insulating shutter closed This latch may be deliberately by passed and the shutter moved to the open position Caution should be observed since the exposed line terminal stabs of the starter may be energized at line potential When the isolating switch is replaced in the structure the latch lever is automatically released to allow the shutter to operate normally Lubricati...

Page 23: ...tenance 16 Initial Insulation Level 16 Inspection After Short Circuit 18 Installation 10 Page Insulation Level 17 Isolating Switch 4 9 Isolating Switch Contactor Interlock 6 Isolating Switch Handle Positions 4 Isolating Switch Maintenance 22 Line Stab Insulating Shutter 6 Low Voltage Components 2 Low Voltage Cut Off Switch 4 Low Voltage Cut Off Switch Replacement 22 Lubrication 22 Magnet Operating...

Page 24: ...I B 48003 Page 24 Effective 11 97 Printed in U S A CCI Cutler Hammer 221 Heywood Road Arden NC 28704 ...

Reviews: