Installation procedure
CBC-8000 capacitor bank control installation and operation instructions
MN916001EN—October 2018
Eaton.com
21
3.
To install the control into a meter socket, follow the
procedure
Socket mount installation on Page 25
. To
install the control on a utility pole, follow the procedure
Pole mount installation on Page 26
.
Note:
Pole mount applications do not use a meter socket.
Table 5. Mounting options.
Mounting Style
Jaw 1
Jaw 2
Jaw 3
Jaw 4
Jaw 5
Jaw 6
Option 1
Line
Neutral
Trip
Close
Option 2
Line
Neutral
Close
Trip
Option 3
SL
a
Neutral
Line
Trip
SH
a
Close
Option 4
Line
Neutral
SL
a
SH
a
Trip
Close
Option 5
Line
Neutral
NSL
a
NSH
a
Trip
Close
Option 6
Line
Neutral
NSH
a
NSL
a
Trip
Close
Option 7
Line
Neutral
NSH
a
CSH
a
Trip
Close
Option 8
Pole mount with standard male 7-pin DIN connector.
Option 9
Pole mount with standard male 14-pin DIN connector.
Option 0
Pole mount with standard male 5-pin DIN connector.
Option A
Custom socket mount – contact Eaton’s Cooper Power series for more information.
Option B
Custom pole mount – contact Eaton’s Cooper Power series for more information.
a. SH is Line Current/Voltage Signal High, SL is Line Current/Voltage Signal Low, NSH is Neutral Current Signal High, NSL is Neutral Current
Signal Low, and CSH is Line Current Signal High. Refer to Figure 27 and Figure 28 for a diagram that shows how the jaws are numbered for
the four-jaw and six-jaw meter socket configurations.
Note:
The sensor inputs are rated for 0 to 10 VAC.