11
Manual CEAG CG-Controller for CG 2000/ZB-S
30080001458 (C) July 2016 www.ceag.de
8 Status display and fault display
8 Status display and
fault display
8.1 Status display
The status display is located on Line 2 in the
main screen (see Table 2).
If a status with a lower priority is being dis-
played and a status with a higher priority occurs,
the newer status with the higher priority will be
displayed.
If this new higher status drops out again, the
old, lower status will be displayed.
By default, the status with the highest priority
will be displayed. If there are additional status
messages, you can display them in the subme-
nu by pressing the ENTER key.
As soon as no more status messages are pen-
ding, “Operation” is displayed.
The status of a previously selected device is
displayed in Line 2 of the Device info menu
according to the same priority.
8.2 Fault display
The fault is located on Line 3 in the main screen
(see Table 3).
The fault of a previously selected device is dis-
played in Line 3 of the Device info menu accor-
ding to the same priority.
8 .2 .1 Sum failure
A sum failure is present if more than one fault
error is present at the same time.
Sum failure = more than one fault
Faults for generating the group fault:
• Battery interrupted
• Battery voltage too high
• Isol., charging module or booster failure 1
• Isol., charging module or booster failure 2
• Isol. failure
• Communication failure
• Luminaire failure
• Minimum duration
8 .2 .1 .1 Example of a sum fault message
A sum fault is displayed if a fault is present, for
example “Battery voltage too high” and
an “Isol., charging module or booster failure 1”
is present.
8 .2 .1 .2 Example of no sum failure message
If a “Battery voltage too high” fault is present,
no group fault is displayed.
8 .2 .2 Display of additional faults
in the “Info device” menu
By default, the fault with the highest priority is
displayed. If there are additional fault messages,
you can display them
in the submenu by pressing the ENTER key.