INSTALLATION
Eaton BladeUPS Bar Installation Guide
S
164201723 Rev 2
www.eaton.com/powerquality
21
15.
BladeUPS Bar 4-High.
Install two M6
12 hex bolts in each of the
bar's two mounting brackets, securing the length of the bar to the
rack. See Figure 16. Torque the bolts to 5.1
±
0.8 Nm (45
±
7 lb in).
16.
BladeUPS Bar 6-High.
Install two M6
12 hex bolts in each of the
bar's three mounting brackets, securing the length of the bar to the
rack. See Figure 16. Torque the bolts to 5.1
±
0.8 Nm (45
±
7 lb in).
17.
Install an M4
8 pan-head screw to secure the wireway top panel
to the bar. See Figure 16.
Rear of Rack
M6
12 Hex Bolts through
Rack to Terminal Block
Assembly Bracket (3 places)
M6
12 Hex Bolts (2 places)
per Mounting Bracket
NOTE
One mounting
bracket shown.
Terminal Block Assembly
Bracket Stud (at position
14 from top)
Front of Rack
Bar
M4
8
Pan-Head Screw
Figure 16. Bar Brackets Installation