RPO connection:
RPO
Note
Port type
Terminal, up to Number 14 AWG
wires
Specifications of
external switches
60 VDC/30 VAC, maximum current:
20 mA
•
Remote On/Off (ROO)
ROO enables remote turning on/off the UPS via a switch.
The UPS will be powered on (or remain on) when the contact point changes from an open circuit to a closed
one.
The UPS will shut down (or remain off) when the contact point changes from a closed circuit to an open one.
ROO connection:
ROO
Note
Port type
Terminal, up to Number 14 AWG
wires
Specifications of
external switches
60 VDC/30 VAC, maximum current:
20 mA
•
Remote control connection and testing
1.
Confirm that the UPS is off and disconnected from the grid.
2.
Remove the screws to remove the RPO terminal from the UPS.
3.
Connect the two pins of the RPO terminal to a always closed passive switch.
Switch is on: Powering off the UPS
To resume normal operation, close the RPO external
switch and restart the UPS via the front panel.
4.
Insert the RPO terminal into the port on the back of the UPS, then tighten the screws.
5.
Connect the UPS as described above and restart the UPS.
6.
Turn on the RPO external switch to test whether the UPS is off.
Make sure you test the RPO to ensure its proper functioning before applying your key load to avoid
unexpected power outages to the load.
Programmable output signals
9PX has 4 output signal ports supporting signal programming: 1 relay output port, and 3 optical coupling
output ports (DB9-1/7/8). These ports can be set to one of the following functions (see Settings >
Communication Settings > Output Signal) on Page 16:
Signal
Default
assignment
Description
Battery mode
DB9-Pin 8
UPS is in Battery mode
Battery voltage is low
DB9-Pin 1
Battery is low and the UPS is about to shut down
Battery fault
-
Battery fault
Bypass
Relay output
(1)
UPS is in Bypass mode
UPS is normal
DB9-Pin 7
Load is energized (power supplied by inverter or bypass), with
no alarms.
UPS has output
-
Load is energized (power supplied by inverter or bypass).
Always closed
Summary of Contents for 9PX 1000i
Page 10: ...9PX EBM 48V 9PX EBM 72V 2U 9PX EBM 72V 3U 12 电池连接端口 13 外接电池箱数量侦ð端口 ...
Page 21: ... 调整LCD面板和EATON标识的方向 调整LCD面板的视角 ...
Page 22: ...3 6 机 机 机 机架 架 架 架式 式 式 式安 安 安 安装 装 装 装 UPS EBM和选配件模块的机架式安装 请按照步骤1到4将模块安装在导轨上 导轨由伊顿提供 ...
Page 45: ...www eaton com 船用滤波器 3000 VA 安装与用户使用说明书 ...
Page 94: ...www eaton com Marine Filter 3000 VA Installation and user manual ...