![Eaton 9PX 1000i Installation And User Manual Download Page 72](http://html.mh-extra.com/html/eaton/9px-1000i/9px-1000i_installation-and-user-manual_527146072.webp)
3.8
UPS Connection - HotSwap MBP module configured (optional;
standard configuration of the HotSwap model)
The HotSwap MBP module enables UPS servicing or even replacement without powering off the load.
9PX 2200IRT/9PX 3000IRT
:
1.
Use the supplied power
cord
to connect the HotSwap
MBP's input socket
to the AC
power supply.
2.
Use the supplied power
cord
to connect the UPS input
socket
to the HotSwap MBP's
"UPS Input" socket
.
Both the
power cord and the connecting
socket are marked in blue.
3.
Use the supplied power
cord
to connect the UPS
socket
to the HotSwap MBP's
"UPS Output" socket
.
Both
the power cord and the
connecting socket are marked in
red.
4.
Connect the load to
the
sockets
and
of the
HotSwap MBP.
These sockets
vary depending on the HotSwap
MBP version.
Attention: Do not use the UPS
output socket to power the
load, as the power supply to
the UPS output may be cut out
when the HotSwap MBP knob
is in bypass.
9PX 1000IRT/9PX 1500IRT
:
An additional power cord
accessory is required to connect
the UPS and MBP; sold
separately.
Follow the same steps as for
9PX 2200IRT/9PX 3000IRT and
note the blue and red markings.
Load
Summary of Contents for 9PX 1000i
Page 10: ...9PX EBM 48V 9PX EBM 72V 2U 9PX EBM 72V 3U 12 电池连接端口 13 外接电池箱数量侦ð端口 ...
Page 21: ... 调整LCD面板和EATON标识的方向 调整LCD面板的视角 ...
Page 22: ...3 6 机 机 机 机架 架 架 架式 式 式 式安 安 安 安装 装 装 装 UPS EBM和选配件模块的机架式安装 请按照步骤1到4将模块安装在导轨上 导轨由伊顿提供 ...
Page 45: ...www eaton com 船用滤波器 3000 VA 安装与用户使用说明书 ...
Page 94: ...www eaton com Marine Filter 3000 VA Installation and user manual ...