Safety Instructions
Safety of persons
•
The system has its own power source (the battery). Consequently, the power outlets may be ener-gized
even if the systems is disconnected from the AC power source. Dangerous voltage levels are present
within the system. It should be opened exclusively by qualified service personnel.
•
The system must be properly grounded at all times.
•
The battery supplied with the system contains small amounts of toxic materials. To avoid accidents, the
directives listed below must be observed:
- Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries
and the required precautions.
- When replacing batteries, replace with the same type and number of batteries or battery packs.
- Do not dispose of batteries in a fire.The batteries may explode.
- Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high.
•
Precautions must be taken for all handling:
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect charging source prior to connecting or disconnecting battery terminals.
- Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from
ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of
such shock can be reduced if such grounds are removed during installation and maintenance
(applicable to equipment and remote battery supplies not having a grounded supply circuit).
Product Safety
•
To connect the UPS, instructions and operation described in the manual must be followed in the indicated
order.
•
CAUTION -To reduce the risk of fire, the unit connects only to a circuit provided with 20 or 30 amperes
maximum branch circuit overcurrent protection in accordance with the National Electric Code,
ANSI/NFPA 70 (US installations only).
•
Check that the indications on the rating plate correspond to your AC powered system and to the actual
electrical consumption of all the equipment to be connected to the system.
•
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall be
easily accessible
•
Never install the system near liquids or in an excessively damp environment.
•
Never let a foreign body penetrate inside the system.
•
Never block the ventilation grates of the system.
•
Never expose the system to direct sunlight or source of heat.
•
If the system must be stored prior to installation, storage must be in a dry place.
•
The admissible storage temperature range is -25ºC to +55ºC without batteries, 0°C to 40°C with
batteries.
•
The system is not for use in a computer room AS DEFINED IN the standard for the Protection of
Information Technology Equipment, ANSI/NFPA 75 (US installations only). Contact Eaton resellers to
order a special battery kit, if needed to meet the ANSI/NFPA 75 requirement.
Summary of Contents for 9PX 1000i
Page 10: ...9PX EBM 48V 9PX EBM 72V 2U 9PX EBM 72V 3U 12 电池连接端口 13 外接电池箱数量侦ð端口 ...
Page 21: ... 调整LCD面板和EATON标识的方向 调整LCD面板的视角 ...
Page 22: ...3 6 机 机 机 机架 架 架 架式 式 式 式安 安 安 安装 装 装 装 UPS EBM和选配件模块的机架式安装 请按照步骤1到4将模块安装在导轨上 导轨由伊顿提供 ...
Page 45: ...www eaton com 船用滤波器 3000 VA 安装与用户使用说明书 ...
Page 94: ...www eaton com Marine Filter 3000 VA Installation and user manual ...