![Eaton 9PX 1000i Installation And User Manual Download Page 63](http://html.mh-extra.com/html/eaton/9px-1000i/9px-1000i_installation-and-user-manual_527146063.webp)
Discharge
Protection
[Yes] [No]
If it is set to [Yes], the UPS will automatically
adjust the battery voltage threshold at the end
of battery discharge to prevent the battery from
deep discharge.
It set to [No], it will void the warranty.
[Yes]
Communication
Settings
Input Signal
[ROO] [RPO] [DB9-4]
Parameters of the input signal (function, delay,
and active level) can be set. Its function is
implemented through an external contact point
or the RS232 port.
ROO port:
- [Function]: [No] [ROO] [RPO] [Generate
Alarm] [Force Bypass] [Connect Generator]
[Remote Power Off]
[No]
-
[Delay]: [0s] … [999s]
[0s]
- [Effective Time]: [On] [Off]
[Off]
RPO port:
- [Function]: [No] [ROO] [RPO] [Generate
Alarm] [Force Bypass] [Connect Generator]
[Remote Power Off]
[No]
-
[Delay]: [0s] … [999s]
[0s]
- [Effective Time]: [On] [Off]
[On]
DB9-4 port:
- [Function]: [No] [ROO] [RPO] [Generate
Alarm] [Force Bypass] [Connect Generator]
[Remote Power Off]
[No]
-
[Delay]: [0s] … [999s]
[0s]
- [Effective Time]: [High] [Low]:
[High]
Communication
Settings
Output Signal
[Switch Output] [DB9-1] [DB9-7] [DB9-8]
Sets the output signal parameters at the
occurrence of an event or fault through an
external contact point or the RS232 port.
- [Switch Output]: [Battery Mode ] [Low Battery
Voltage] [Battery Fault] [Bypass] [UPS Normal]
[Load Protected] [UPS with Output] [General
Alarm] [External Charger] [Overload Alarm]
[Switch Output]:
[Bypass]
- [DB9-1]: [Battery Mode ] [Low Battery Voltage]
[Battery Fault] [Bypass] [UPS Normal] [Load
Protected] [UPS with Output] [General Alarm]
[External Charger] [Overload Alarm]
[DB9-1]: [Low Battery
Voltage]
- [DB9-7]: [Battery Mode ] [Low Battery Voltage]
[Battery Fault] [Bypass] [UPS Normal] [Load
Protected] [UPS with Output] [General Alarm]
[External Charger] [Overload Alarm]
[DB9-7]: [UPS
Normal]
- [DB9-8]: [Battery Mode ] [Low Battery Voltage]
[Battery Fault] [Bypass] [UPS Normal] [Load
Protected] [UPS with Output] [General Alarm]
[External Charger] [Overload Alarm]
[DB9-8]: [Battery
Mode]
Remote
Command
[Enabled] [Disabled]
If Remote Command is set to [Enabled], the
Shutdown or restart command from the
software will be allowed to be executed.
[Enabled]
Summary of Contents for 9PX 1000i
Page 10: ...9PX EBM 48V 9PX EBM 72V 2U 9PX EBM 72V 3U 12 电池连接端口 13 外接电池箱数量侦ð端口 ...
Page 21: ... 调整LCD面板和EATON标识的方向 调整LCD面板的视角 ...
Page 22: ...3 6 机 机 机 机架 架 架 架式 式 式 式安 安 安 安装 装 装 装 UPS EBM和选配件模块的机架式安装 请按照步骤1到4将模块安装在导轨上 导轨由伊顿提供 ...
Page 45: ...www eaton com 船用滤波器 3000 VA 安装与用户使用说明书 ...
Page 94: ...www eaton com Marine Filter 3000 VA Installation and user manual ...