![background image](http://html1.mh-extra.com/html/eaton/9476-et/9476-et_instruction-manual_3897056015.webp)
11
INM 9476-ETG Rev 2
13
CONNECTING THE 9476-ET(G)TO A PC/NETWORK
Ensure that the 9476 unit is powered by a suitable IS supply, such as the MTL
9492-PS-PLUS. PoEx can be used to power the unit via the LAN port if required.
The 9476 unit should then be connected to an IS Ethernet Network/PC using a
suitable CAT5/6 cable. Either LAN Port 1 or 2 can be used. The other LAN port can
be used for daisy chaining units together.
Run the 9461-ET Finder.exe program which can be found on the MTL website, this
will automatically search for and locate any 9476 units connected to the network
Click on the device that you are looking to configure, then click the “configure IP
settings” button and this will bring up the following screen
Manually type in the settings that you require and then enter the password “CSL”.
Click the apply button to send the settings to the 9476.
Reboot the device by either powering down or by clicking the “reboot” button in
the above screen.
Once the 9476 is up and running, navigate to the IP Address that has been
programmed into the unit using a web browser
NOTE: The Factory Default IP Address is 192.168.0.200