Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
53
Table 20. Power Cable Conduit Recommendations (Continued)
UPS Model
UPS
Rating
Voltage
Terminal
Number
of Wires
in Conduit
Minimum
Conduit
Trade Size
(inches)
Number
of
Conduits
93PM-L 200-8
93PM-L 200-9 (N+1)
160 kW
208 or 220
Vac
AC Input to UPS
Rectifier
(A, B, C, Ground))
4
2-1/2
3
AC Input to UPS Bypass
(A, B, C, Neutral, Ground
6
3
3
208 Vac
220 Vac
AC Output
(A, B, C, Neutral,
Ground)
6
3-1/2
4
3
2
DC
Battery
(Positive, Negative,
Ground)
6
2
2
93PM-L 200-9
93PM-L 200-10 (N+1)
170 kW
208 or 220
Vac
AC Input to UPS
Rectifier
(A, B, C, Ground)
4
2-1/2
3
AC Input to UPS Bypass
(A, B, C, Neutral, Ground
6
3
3
AC Output
(A, B, C, Neutral,
Ground)
6
3-1/2
3
DC
Battery
(Positive, Negative,
Ground)
6
2
2
93PM-L 200-9
93PM-L 200-10 (N+1)
180 kW
208 or 220
Vac
AC Input to UPS
Rectifier
(A, B, C, Ground)
4
2–1/2
3
AC Input to UPS Bypass
(A, B, C, Neutral, Ground
6
3
3
AC Output
(A, B, C, Neutral,
Ground)
6
3-1/2
3
DC
Battery
(Positive, Negative,
Ground)
6
2
2
Summary of Contents for 93PM-L IAC-B
Page 162: ...16400072401 164000724 01 ...