36
Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
Table 11. Input/Output Ratings and Wiring Recommendations: 110–150 kW (220/220) (Continued)
AC Output to Critical Load (Four
Wire)
Full Load Current
(3) Phases – see Note, (1) Ground
D
Amps
289
315
341
367
394
Neutral Current
Amps
500
545
591
636
682
Minimum Conductor Size (Phase A, B,
and C, and Neutral)
Number per Phase
AWG or
kcmil
(each)
300 MCM
(2)
300 MCM
(2)
350 MCM
(2)
400 MCM
(2)
500 MCM
(2)
Neutral Wire Size
Number
AWG or
kcmil
(each)
250 MCM
(4)
300 MCM
(4)
300 MCM
(4)
350 MCM
(4)
400 MCM
(4)
Minimum Conductor Size (Ground)
Number
–
AWG or
kcmil
(each)
2
(2)
2
(2)
2
(2)
1/0
(2)
1/0
(2)
NOTE
Callout letters
A
,
B
,
C
and
D
map to
Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM-L Integrated Battery
Cabinet (IBC).
Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated
UPS kW frame size installed.