Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
51
Table 20. Power Cable Conduit Recommendations (Continued)
UPS Model
UPS
Rating
Voltage
Terminal
Number
of Wires
in Conduit
Minimum
Conduit
Trade Size
(inches)
Number
of
Conduits
93PM-L 200-5
93PM-L 200-6 (N+1)
100 kW
208 or 220
Vac
AC Input to UPS
Rectifier
(A, B, C, Ground)
4
2-1/2
2
AC Input to UPS Bypass
(A, B, C, Neutral, Ground
6
3
2
AC Output
(A, B, C, Neutral,
Ground)
6
2-1/2
2
DC
Battery
(Positive, Negative,
Ground)
3
2
1
93PM-L 200-6
93PM-L 200-7 (N+1)
110 kW
208 or 220
Vac
AC Input to UPS
Rectifier
(A, B, C, Ground)
4
2-1/2
2
AC Input to UPS Bypass
(A, B, C, Neutral, Ground
6
3
2
AC Output
(A, B, C, Neutral,
Ground)
6
2-1/2
2
DC
Battery
(Positive, Negative,
Ground)
3
2
1
93PM-L 200-6
93PM-L 200-7 (N+1)
120 kW
208 or 220
Vac
AC Input to UPS
Rectifier
(A, B, C, Ground)
4
2-1/2
2
AC Input to UPS Bypass
(A, B, C, Neutral, Ground
6
3
2
AC Output
(A, B, C, Neutral,
Ground)
6
3–1/2
2
DC
Battery
(Positive, Negative,
Ground)
3
2
1