7. Ensure that the Group 1 parameters match the application by setting — at minimum, the
following parameters to match the motor nameplate:
●
Nominal voltage of the motor.
●
Nominal nameplate frequency of the motor.
●
Nominal nameplate full load speed of the motor.
●
Motor nominal current.
●
Motor power factor.
●
Motor type (Select PM motor in Group 6 of special app)
8. Perform either Test A or Test B without the motor connected to the SVX9000/SPX9000.
Test A — Control from the Control Panel
●
Apply input power to the SVX9000/SPX9000.
●
Press the keypad START button.
●
If not in the Operate Menu, go to the Monitoring Menu and check that the output
frequency follows the keypad reference.
●
Press the keypad STOP button.
Test B — Control from the I/O Terminals
●
Apply input supply power to the SVX9000/SPX9000.
●
Change control from the keypad to the I/O terminals using the LOCAL/REMOTE
button.
●
Start the drive by closing the START/STOP input on DIN1.
●
Change the frequency reference setting on AI1.
●
If not in the Operate Menu, go to the Monitoring Menu and check that the output
frequency follows the frequency reference.
●
Stop the drive by opening the START/STOP input on DIN1.
9. Disconnect all power to the SVX9000/SPX9000. Wait until the cooling fan on the unit
stops and the indicators on the panel are not lit. If no keypad is present, check the
indicators in the control panel cover. Wait at least five more minutes for the DC bus to
discharge. Connect the motor to the SVX9000/SPX9000. If possible, perform a startup
test or ID run with the motor connected to the SVX9000/SPX9000 but not connected to
the process. If the SVX9000 must be tested with the motor connected to the process,
perform it under no-load conditions.