9000X AF Drives User Manual
MN04001004E
For more information visit:
www.eaton.com
5-11
June 2009
System Menu Parameters
System Menu Copy Parameter Options (S5.3)
The parameter copy function is used when the operator wants to copy one or all parameter
groups from one drive to another. All the parameter groups are first uploaded to the keypad,
then the keypad is connected to another drive and then the parameter groups are
downloaded to it (or possibly back to the same drive).
Note: Before any parameters can successfully be copied from one drive to another, the drive
must be stopped when the parameters are downloaded to it.
S5.1
Language
Selection
Range: English, Spanish, French, Portuguese
Default: English
Language
This parameter offers the ability to control the SVX9000/SPX9000 through the
keypad in the language of your choice. Available languages are: English, Spanish,
French and Portuguese.
S5.2
Application
Selection
Default: Basic
Application
This parameter sets the active application.
When changing applications, you will be asked if you want the parameters of the
new application to be uploaded to the keypad. If you wish to load the new
application parameters, push the ENTER button. Pushing any other button saves the
parameters of the previously used application in the keypad.
S5.3.1
Parameter
Sets
Parameter Sets
This parameter allows you to reload the factory default parameter values, and to
store and load two customized parameter sets.
S5.3.2
Upload to
Keypad
Up to keypad
This function uploads all existing parameter groups to the keypad.
S5.3.3
Download
from Keypad
Range: 0 – 3
Default: 0 (All parameters)
Down from keypad
This function downloads one or all parameter groups from the keypad to the drive.
0
All parameters
1
All, no motor
2
Application parameters
S5.3.4
Automatic
Backup
Range: Yes, No
Default: Yes
Auto.backup
This parameter activates and deactivates the parameter backup function. When the
Parameter backup function is activated, the keypad makes a copy of the parameters
and settings in the currently active application. When applications are changed, you
will be asked if you wish the parameters of the new application to be uploaded to
the keypad. For this to happen, push the ENTER button. If you wish to keep the copy
of the parameters of the previously used application saved in the keypad push any
other button.
Note: Parameters saved in the parameter settings of S5.3.1 will be deleted when
applications are changed. If you want to transfer the parameters from one
application to another you have to upload them to the keypad first.