IL17569
Page 4-8
Effective June, 2001
Current Demand Window (Fixed Window)
Current Demand is the average of system current over time, which can
be set from 1 to 60 minutes. For example, if the range is set for 30
minutes, the FP-5000 calculates the average current over the past 30
minutes and updates the value every 30 minutes. The range can be
selected from the Logging menu by pressing the “
Set
” pushbutton.
Refer to Section 5 Settings of this manual for setting changes. The
default setting for Current Demand window selection is 15 minutes.
Power Demand Window (Fixed or Slide)
In addition to the interval setting as in the Current Demand Window,
the Power Demand window has an additional setting of
Fixed
or
Slide
window. The default setting for Power window is
Fixed
.
If
Fixed
window is selected, the Demand will be calculated every fixed interval
and updated every fixed interval. If the
Slide
window is selected, the
Demand will be calculated every minute for the interval selected. For
example, if the
Slide
window is selected and the interval is set to 30
minutes, the FP-5000 calculates and updates the average power for
the past 30 minutes, every minute. Refer to Section 5 Settings of this
manual for setting changes.
The FP-5000 also saves the peak demand values for current and
power. The quantities represent the largest demand value since the
demand values were last reset. Peak demands for current and
system power are date and time stamped to the nearest second.
Current Peak Demand
IA Demand
Magnitude
IB Demand
Magnitude
IC Demand
Magnitude
I Demand Last Reset
Date
mm/dd/yy
Time
hh:mm:ss
Power Demand
M Watt
Magnitude
M Var
Magnitude
M VA
Magnitude
Power Peak Demand
M Watt
Magnitude
M Var
Magnitude
M VA
Magnitude
P Demand Last Reset
Date
mm/dd/yy
Time
hh:mm:ss
Current Demand
IA Demand Magnitude
IB Demand Magnitude
IC Demand Magnitude
•
Power Distribution (
Figures 4.4
and
4.6
)
Three conditions are typically encountered when monitoring power
distribution systems as follows:
1.
Circuit breakers A and B are closed and C is open.
Power flow is in Quadrant 4. The power factor and Vars
are positive.
2.
Circuit breakers A and C are closed and B is open.
Power flow for breakers A and C is in Quadrant 4. The
power factor and Vars are positive.
3.
Circuit breakers B and C are closed and A is open. The
power flow for breaker B is in Quadrant 4 and the
metering conditions are the same as conditions 1 and 2.
However, the power flow for breaker C is reversed and
is in Quadrant 2.
The display units for Energy may be set to either kilo units or Mega
units. The “Energy Unit” setting is changed in the “System Configu-
ration” setting menu in the “Set” mode. The screen displays a 9-digit
energy reading. Energy values roll over from 999,999,999 to 0.
4.6.1.4 Selecting the “Demand” Sub-menu
This menu allows the user to view the following Demand parameters
(See
Display 4.7
).
• Current Demand (IA, IB, IC)
• Current Peak Demand (IA, IB, IC)
• Date and Time Stamp when Current Demand was last reset
• Power Demand (Watt, Var, VA)
• Power Peak Demand (Watt, Var, VA)
• Date and Time Stamp when Power Demand was last reset
Figure 4-5. Induction Motor Load
Figure 4-6. Power Distribution
Display 4.7 Demand Sub-menu
Summary of Contents for 66D2041G01
Page 1: ...IL17569 Effective June 2001 Instructions for FP 5000 Protective Relay ...
Page 7: ...IL17569 Table of Contents 6 Effective June 2001 This page left blank intentionally ...
Page 13: ...IL17569 Page 2 2 Effective June 2001 Figure 2 2 FP 5000 Simple Wye Connected Application ...
Page 14: ...Page 2 3 IL17569 Effective June 2001 Figure 2 3 FP 5000 Simple Open Delta Application ...
Page 19: ...IL17569 Page 2 8 Effective June 2001 This page left blank intentionally ...
Page 25: ...IL17569 Page 3 6 Effective June 2001 This page left blank intentionally ...
Page 98: ...IL17569 Page 5 50 Effective June 2001 This page left blank intentionally ...
Page 108: ...IL17569 Page 6 10 Effective June 2001 Figure 6 10 Common Ct Wiring Configurations ...
Page 141: ...IL17569 Page 11 4 Effective June 2001 This page left blank intentionally ...
Page 165: ...IL17569 Page Appendix 6 Effective June 2001 Figure 13 2 ANSI Very Inverse ...
Page 166: ...Page Appendix 7 IL17569 Effective June 2001 Figure 13 3 ANSI Extremely Inverse ...
Page 167: ...IL17569 Page Appendix 8 Effective June 2001 Figure 13 4 IEC A Figure 13 4 IEC A ...
Page 168: ...Page Appendix 9 IL17569 Effective June 2001 Figure 13 5 IEC B ...
Page 169: ...IL17569 Page Appendix 10 Effective June 2001 Figure 13 6 IEC C ...
Page 170: ...Page Appendix 11 IL17569 Effective June 2001 Figure 13 7 IEC ...
Page 171: ...IL17569 Page Appendix 12 Effective June 2001 Figure 13 8 ANSI ...
Page 172: ...Page Appendix 13 IL17569 Effective June 2001 Figure 13 9 Thermal ...
Page 173: ...IL17569 Page Appendix 14 Effective June 2001 Figure 13 10 Phase I4 t ...
Page 174: ...Page Appendix 15 IL17569 Effective June 2001 Figure 13 11 Phase I2 t ...
Page 175: ...IL17569 Page Appendix 16 Effective June 2001 Figure 13 12 Phase It ...
Page 176: ...Page Appendix 17 IL17569 Effective June 2001 Figure 13 13 Phase 12 I4 t ...
Page 177: ...IL17569 Page Appendix 18 Effective June 2001 Figure 13 14 Phase I2 t ...
Page 178: ...Page Appendix 19 IL17569 Effective June 2001 Figure 13 15 Ground IT ...
Page 180: ...Page Appendix 21 IL17569 Effective June 2001 This page left blank intentionally ...
Page 187: ...Publication No IL17569 June 2001 Pittsburgh Pennsylvania U S A ...