8
Instruction Booklet
IB0191002EN
Effective November 2019
EAFR-101C arc point sensor relay
user manual
EATON
www.eaton.com
4.1.2 EAFR-01 point sensor technical data
Table 4. EAFR-01 point sensors technical data.
Light intensity threshold
8,000 Lux/25,000 Lux/50,000 Lux
Detection radius
180 degrees
Mechanical protection
IP 64
Sensor wiring arrangement
Two wires and shield
Sensor cable specification
Shielded twisted pair 0.52 mm
2
(0.0008 in.
2
)
Maximum sensor cable length per
sensor channel
200 m (656 ft)
Operating temperature
-20 to 85°C (-4 to 185°F)
5 System self-supervision
The EAFR-101C includes an extensive self-supervision feature .
Self-supervision includes both internal functions and external
connections . The self-supervision module monitors power supply,
hardware, and software malfunctions, and binary input connection
and sensor problems . Dipswitch settings are also supervised by
comparing the actual value with stored non-volatile memory data
(see Section 3 .3 .1: Auto configuration [System setup]) .
In a healthy condition, the POWER LED is on and the System Failure
(SF) relay is energized . If the self-supervision function detects a
faulty condition or the power supply fails, the self-supervision relay
is released and the ERROR LED is illuminated .
If a sensor failure occurs, the relay will go into ERROR mode . The
ERROR LED will illuminate, the SF relay will release, and the corre-
sponding faulty SENSOR CHANNEL LED will start blinking . In this
situation, the relay is still in the protection mode, but with the faulty
sensor channel blocked . If the error is resolved, the ERROR LED
will automatically clear the SF-status and failed SENSOR CHANNEL
LED will remain in blinking status . This means that the SF relay will
energize and the ERROR LED will turn off . If one or more of the
sensors are disconnected, the healthy sensors remain in use and
relay remains operational . The EAFR-101C will remain in error mode
until the disconnected sensors are repaired .
If a dipswitch setting is changed after the auto-configuration function
(see Section 3 .3 .1: Auto configuration [System setup]) has been
executed, the relay will go into SF alarm mode . The configured
(stored) setting is however still valid and the relay is still operational .