6
Instruction Booklet
IB0191002EN
Effective November 2019
EAFR-101C arc point sensor relay
user manual
EATON
www.eaton.com
Table 2. EAFR-101 dipswitch setting selection.
Dipswitch
Function selection
ON (left position)
OFF (right position)
8
Point sensor channels S1,S2 trip criteria.
Trip on light only. (L)
Trip on light and over-current. (L+C)
Both signals are required simultaneously
to trip.
7
Point sensor channel S3,S4 trip criteria.
Trip on light only. (L)
Trip on light and over-current. (L+C)
Both signals are required simultaneously
to trip.
6
Latch or non-latch for trip relays T1 and
T2.
T1 and T2 operate as latched.
T1 and T2 operate as non-latched.
ote:
N
Trip relay T3 is always latched . Binary output BO1 (light out) function is
always non-latched .
5
Binary Input 1 & 2 activation. CB in use/
not in use.
CB in use.
CB not in use.
4
Binary Input 3&4 activation. CB in use/
not in use.
CB in use.
CB not in use.
3
Binary Input 5 function selection.
Master trip.
Current.
2
Configuration selection.
1
Configuration selection.