8 Technical data
ESR5-NOS-31-230VAC
12/19 MN049013EN
www.eaton.com
13
General data
Relay type
Electromechanically forcibly guided, dust-proof relay
Nominal operating mode
100 % operating factor
Degree of protection
IP20
Minimum degree of protection of inst. location
IP54
Mounting position
any
Mounting type
DIN rail mounting
Type of housing
Polyamide PA non-reinforced yellow
Air and creepage distances between the power circuits
DIN EN 50178/VDE 0160
Rated insulation voltage
250 V AC
Rated surge voltage / insulation
4 kV / basic insulation (safe isolation, reinforced insula-
tion, and 6 kV between A1-A2/logic/enabling and
signaling current paths)
Pollution degree
2
Surge voltage category
III
Dimensions
W x H x D
22.5 x 99 x 114.5 mm
Connection data
Conductor cross section, solid
0.2 mm
2
- 2.5 mm
2
Conductor cross section, stranded
0.2 mm
2
- 2.5 mm
2
Conductor cross section AWG/kcmil
24
- 12
Stripping length
7 mm
Ambient conditions
Ambient temperature (operation)
-20 °C - 55 °C
Ambient temperature (storage/transport)
-40 °C - 85 °C
Max. permissible relative humidity (operation)
75 %
Max. permissible humidity (storage/transport)
75 %
Certification / Approvals
Approvals
Safety data
Stop category according to IEC 60204-1
0
Safety parameters for IEC 61508 - High demand
SIL
1
PFH
d
2.42 x 10
-10
per hour
Demand rate
< 12 months
Proof test interval
240 months
Duration of use
240 months
ID 0600000000
Product Safety
Functional
Safety