![Eaton 153152 Manual Download Page 18](http://html1.mh-extra.com/html/eaton/153152/153152_manual_526689018.webp)
8 Technical data
14
ESR5-NOS-31-230VAC
12/19 MN049013EN
www.eaton.com
The specifications are valid if the safety function required once per year.
The specifications apply assuming the following calculation basis:
B
10d
300000 (at 5
A DC-13)
Cycles
8760 per year
Safety parameters for IEC 61508 - Low demand
SIL
1
PFD
avg
5.73 x 10
-5
Proof test interval
36 months
Safety characteristic data according to EN ISO 13849
Category
1
Performance Level
c
Duration of use
240 months
The specifications apply assuming the following calculation basis:
B
10d
300000 (at 5
A DC-13)
Cycles
8760 per year
Safety characteristic data according to EN 62061
SILCL
1