50/75/150 VCP-W

Selectable Ground and Test Device

4.6 DEVICE AMPERAGE CONVERSION PROCEDURE

The VCP-W-SGT may be optionally provided with interchangeable 

primary disconnects. When so equipped, the extra primary 

disconnects and code plates are boxed separately.
The primary circuit terminals of the selectable ground and 

test device consists of silver plated copper conductors with 

interchangeable primary disconnects. The same primary 

disconnects are used for 1200 and 2000 ampere applications; the 

SG&T must be converted for 3000 ampere SG&T use. Primary 

disconnecting contacts are bolted to the lead assemblies; these 

primary disconnects are configured to engage the circuit breaker 

compartment primary disconnects. It is critical to confirm that 

1200/2000 ampere primary disconnects are installed prior to 

insertion in 1200/2000 ampere circuit breaker compartments; 

likewise for tests in 3000 ampere circuit breaker compartments. 

THIS CONVERSION ALSO REQUIRES A CODE PLATE CHANGE 

PRIOR TO RACKING THE SG&T INTO ITS CIRCUIT BREAKER 

COMPARTMENT.

 Follow the procedure below to convert from one 

primary current design to the other.
a. With the selectable ground and test device located in an 

appropriate work area, remove the existing primary disconnects 

installed on the SG&T. Retain the hardware for re-use. Figure 4.3.

b. After removing the primary disconnect assembly, locate the 

primary disconnects to be installed and install them on the 

lead assemblies using the hardware just removed. The primary 

disconnects just removed should be properly stored to avoid 

potential damage. Figure 4.4.

otee:

N

Ensure shims are installed as shown in Figure 4.5 for the 3000A 

configuration.

c. THE GROUND AND TEST CODE PLATE MUST BE CHANGED AT 

THIS TIME. The SG&T device will be blocked from full insertion in 

the circuit breaker compartment until the code plate is changed. 

The code plate is a mandatory safety feature that must not be 

removed and/or discarded.

d. Left hand and right hand code plates are installed on the lower 

part of the SG&T frame below ‘C’ phase. The right hand code 

plate is mounted adjacent to rail to which the wheels are 

attached; the left hand code plate is mounted to the left of the 

right hand code plate. The left hand code plate is used for the 

continuous current rating, the right hand code plate corresponds 

to the short circuit capabilities of the device. Eaton offers many 

code plate combinations for accepting or rejecting devices 

based on their continuous current rating, short circuit current 

rating, speed of contact parting (3-cycle or 5-cycle) and other 

classifications; consult your Eaton representative for complete 

code plate availability. Table 4.1 provides the code plate 

information for 15 kV SG&T devices that have a short time rating 

of 50 kA. 

Table 4.   

Nominal Voltage  /       

Short Time Rating

Cubicle Current 

Rating

Cycle

Class

Device LH Code

LH Style Code 

Plate

Device RH Code

RH Style Code 

Plate

15 / 50

1200

5

K = 1

12000

8061A47H06

10012

8061A42H01

15 / 50

2000

5

K = 1

11000

8061A38H06

10012

8061A42H01

15 / 50

3000

5

K = 1

20000

8061A40H06

10012

8061A42H01

Examplee: 

If the SG&T is to be used only in switchgear rated for 48-49 kA, only the Left Hand code plate would be changed to allow insertion of the 1200A, 

2000A, or 3000A configured device.

Figure 4.9. 50/75/150 VCP-W with optional LINE/LOAD and 

PHASE labels

Summary of Contents for 150 VCP-W-SGT

Page 1: ...Instruction Book IB182312EN 50 75 150 VCP W Selectable Ground and Test Device 150 VCP W SGT June 2016 Supersedes October 2015 Effective...

Page 2: ...an Eaton sales office should be consulted Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agree...

Page 3: ...4 2 BUSHINGS AND DISCONNECTING CONTACT ASSEMBLIES 11 4 3 GROUNDING CONTACTS 11 4 4 BREAKER CELL CODING PLATES 11 4 5 CELL POSITION DESCRIPTION 11 4 6 DEVICE AMPERAGE CONVERSION PROCEDURE 13 SECTION 5...

Page 4: ...N AND VAST VARIETY OF SYSTEM USER REQUIREMENTS SPECIFIC SAFE OPERATING PROCEDURES FOR THE USE OF THIS DEVICE MUST BE DEVELOPED BY THE USER WARNING SATISFACTORY PERFORMANCE OF SELECTABLE GROUND AND TES...

Page 5: ...able Ground and Test Device Dimensions Breaker Type Sized For Circuit Breaker Compartment Amps A B C D E F G H I J K 150 VCP W 500 Dual 1200 2000 28 50 26 76 10 00 27 81 12 00 14 13 20 88 24 63 2 25 2...

Page 6: ...n the device Failure to do so could result in electrical shock leading to death severe personnel injury or property damage Do not leave the selectable ground and test device in an intermediate positio...

Page 7: ...Services System office Tools and Accessories Racking Handle The racking handle is used to drive the racking mechanism which moves the SG T device into and out of the cell This racking handle is the s...

Page 8: ...g objects excessive moisture etc must be provided Container should be arranged to permit free circulation of air on all sides and temporary heaters should be used to minimize condensation Moisture can...

Page 9: ...ront External View of 150 VCP W SG T Device 3 2 1 8 5 4 7 6 Front External View 150 VCP W SG T Shown 1 Lock out Tag out Ring 4 KirkTM Key Interlock 7 Lift Pull Handle 2 Friction Hinge 5 Spring Loaded...

Page 10: ...une 2016 www eaton com 50 75 150 VCP W Selectable Ground and Test Device Figure 3 3 b Rear External View of 150 VCP W SG T Device Back External View 150 VCP W SG T Shown 1 Lifting Point 2 Primary Disc...

Page 11: ...als in the switchgear compartment Figure 3 5 4 3 GROUNDING CONTACTS The grounding contact is an assembly of spring loaded fingers which ground the device by engaging the switchgear cell grounding bus...

Page 12: ...4 5 Primary Disconnect Shim Removal 3000A Figure 4 8 Primary Disconnect Installed 1200A 2000A Figure 4 6 Primary Disconnect Installation 1200A 2000A Figure 4 4 Primary Disconnect Removal 3000A Figure...

Page 13: ...roperly stored to avoid potential damage Figure 4 4 Note N Ensure shims are installed as shown in Figure 4 5 for the 3000A configuration c THE GROUND AND TEST CODE PLATE MUST BE CHANGED AT THIS TIME T...

Page 14: ...IN THE NEUTRAL POSITION b For SG T devices equipped with Kirk Locks on the terminal access doors use the Kirk key provided to release the special bolt that is held by the Kirk locking system Slide th...

Page 15: ...5 3 Selector Blade Figure 5 6 Utilizing Hot Stick To Engage Selector Blade Figure 5 5 Selector Blade Disengaged Shown in Upper Position Figure 5 7 Selector Blade Engaged Shown in Upper Position Figure...

Page 16: ...IER WHEN PUSHING A SG T INTO A CELL FAILURE TO DO SO COULD RESULT IN BODILY INJURY IF FINGERS BECOME WEDGED BETWEEN THE SG T AND THE CELL USE BOTH FULLY OPENED HANDS FLAT ON THE FRONT OF THE SG T TO A...

Page 17: ...e In Connect Position Figure 5 12 Removing SG T using Lift Pull Handle To remove the SG T from the cell install the extension guide rails Pull up on the Lift Pull Handle as shown in Figure 5 12 then p...

Page 18: ...uired to cut dirt used Stoddard s Solvent Eaton part number 55812CA or commercial equivalent Hardware Visually inspect all hardware Replace any damaged or missing hardware with parts equivalent to tho...

Page 19: ...ating experience 7 1 1 ORDERING INSTRUCTIONS 1 Always specify the selectable ground and test device rating information and general order number from the nameplate 2 Describe the item give the style nu...

Page 20: ...ulevard Cleveland OH 44122 United States Eaton com 2016 Eaton All Rights Reserved Printed in USA Publication No IB182312EN June 2016 Eaton is a registered trademark All trademarks are property of thei...

Reviews: