ICC / ICU SYSTEM INSTALLATION MANUAL
January2005: E\Manuals\Others\Qualitair\ICC\0412115B
7
5. LOCATION & MOUNTING OF OUTDOOR UNIT (ICU)
Figure 5.1 – ICU Unit Positioning
Figure 5.3 – ICU Wall Bracket Fixing
Table 5.1 – ICU Wall Mount Kit Fixing
ICU30
ICU40
ICU55
ICU80
Width mm
720
720
800
800
Height mm
610
610
765
765
Depth mm
250
250
320
320
Weight kg
42
42
60
64
Dim ‘y’ mm
220
220
290
290
Dim ‘Z’ mm
670
670
750
750
Figure 5.2 – ICU Unit Fixing
5.1 Location
The unit can either be mounted on a level surface or suspended from a vertical wall using the
Qualitair wall mounting Optional kit (1). The unit should always be mounted on a load bearing wall
and not a partition wall. Ensure there is sufficient free area around the unit as detailed in Figure 5.2.
5.2 Fixing
Two-off hole fixings (2) and two-off slot fixings (3) suitable for M10 fixings are provided in the base of
the unit to secure the unit to a suitable plinth, or to the wall mount bracket kit. If required, the
contractor should install the unit on anti-vibration pads.
5.3 Service
Connections
The refrigerant pipe (4) and electrical connections (5) are located at the right hand end of the unit.
Ensure there is adequate air entry at the back of the unit as detailed in Figure 5.2 above.
SPECIAL NOTE
ENSURE CONDENSER HAS ADEQUATE CLEARANCE AROUND IT AND IS NOT AFFECTED BY
NEIGHBOURING CONDENSING UNITS AND OTHER OBSTRUCTIONS.