Zone Control:
If the system is Air Zoned, the Zone Override terminal “D” should be used and
will send 24 volts out during the 5-minute maintenance cycle (see 4) only. The 24 volt signal
can be used to open zones to prevent high static pressure and noise from the duct system
during the maintenance mode.
Please contact ETI on how to use the 24 volt signal for your
Zone Board of choice.
6) Auxiliary Heat and Dual Fuel: There is a factory-installed jumper on the field wiring terminal
block between terminals “A” and “S”. This selects the Auxiliary heat source operation. With the
jumper installed, the unit will function with an Auxiliary heat strip as normal. To activate Duel
Fuel mode, the jumper between terminals “A” and “S” should be removed. Once the Auxiliary
heat call is completed, a 5-minute cool down timer prevents the compressor from restarting on
a “Y1 or “Y2”” call until the time elapses. This allows time for the furnace to cool down so that
hot air does not cause high discharge pressure or a lockout condition when the compressor
restarts. The same 20-minute Auxiliary heat timer applies to dual fuel mode as well.
7) Thermostat Selection: The Nano-PLC is compatible with most heat/cool thermostats and zone
boards. The minimum requirement for the thermostat if to be a single stage heat/cool
thermostat. In this case, the Nano-PLC will control all staging functions such as second stage
and Auxiliary Heat as described above.
Summary of Contents for Prime Series
Page 15: ...PSC QS 10 16 Page 15 Figure 8a PSC Compressor Electrical Schematic 230 1 60...
Page 16: ...PSC QS 10 16 Page 16 Figure 8b PSC Compressor Unit Electrical Schematic 230 3 60...
Page 17: ...PSC QS 10 16 Page 17 Figure 9 PSC Air Heating Cooling System Application...
Page 18: ...PSC QS 10 16 Page 18 Figure 10 PSC Air Heating Cooling System Field Wiring Diagram...
Page 26: ...PSC QS 10 16 Page 26 Figure 14 Disassembled Plug Connector...
Page 33: ...PSC QS 10 16 Page 33 Figure 23 PSC Internal Flow Schematic...
Page 34: ...PSC QS 10 16 Page 34 Figure 24 PSC Piping...
Page 36: ...PSC QS 10 16 Page 36 Figure 25 Evacuation of PSC System...
Page 38: ...PSC QS 10 16 Page 38 Figure 26 Initial Charge of PSC System...
Page 40: ...PSC QS 10 16 Page 40 Figure 27 Final Charge of PSC System...
Page 43: ...PSC QS 10 16 Page 43 Figure 31 Start Up Process...
Page 52: ...PSC QS 10 16 Page 52...
Page 53: ...PSC QS 10 16 Page 53...
Page 54: ...PSC QS 10 16 Page 54...
Page 55: ...PSC QS 10 16 Page 55...
Page 56: ...PSC QS 10 16 Page 56...
Page 57: ...PSC QS 10 16 Page 57...