GAS CONNECTIONS
Installation Personnel: Check all connections and fittings on valves and tubing supplied as a part of this unit to
make sure they did not come loose during shipment. A manual gas valve should be provided upstream within 6
feet of the appliance for shutting the gas off during servicing. A ground joint union should be provided between
the house plumbing and the gas inlet to the appliance. A gas pressure regulator has been provided as a part of
this appliance. It is factory pre-set for natural gas and is field adjustable for liquid propane gas. All plumbing
should be clean and free of burrs and metal chips. All pipe connections should be made using a pipe joint
compound resistant to the action of LP gases. A drip TEE must be used to collect any moisture or dirt in the
gas. Upon completing the installation of this appliance, all the gas connections must be checked for gas leaks.
Use a solution of liquid dishwashing soap and water to check for leaks.
This installation must conform with local codes, or in the absence of local codes with the National Fuel Gas Code
ANSI Z223.1/NFPA-54, National Gas and Propane Installation Code, and CSA-B149.1 as applicable.
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in excess of 1/2 psig (3.45 kPa). The appliance must be
isolated from the gas supply piping system by closing it’s individual manual shutoff valve during any pressure
testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.45 kPa).
Provisions for proper air supply must be taken into account when installing the unit. Care should be taken so as
not to obstruct the area in front, under or in rear of the unit. DO NOT PLACE BACK OF THE UNIT CLOSER THAN
6˝ (153mm) TO A WALL OR OTHER SURFACES. The appliance shall be located with respect to other equipment
so it will have adequate clearances for servicing and proper operation.
This unit is supplied with four (4) adjustable feet, which must be installed prior to operation. Four (4)
threaded openings are provided on bottom of the unit to accept the threaded portion of the feet. Screw in the
feet and tighten them securely. During operation, check the feet every sixty (60) days to assure that they are
tight. Failure to use the feet will void warranty and could cause unsafe conditions.
Note: Appliance must be installed under a ventilation hood.
3
INSTALLATION/OPERATING INSTRUCTIONS
Gas Charbroilers
(continued on Page 4)
SERIES
ORIFICE DRILL SIZE / EAGLE PART #
INCHES IN WATER COLUMN
NATURAL
LP
NATURAL
LP
CLCHRB
32 / 336254
50 / 336007
6˝
10˝
CLCHRBL
39 / 361984
51 / 360322
6˝
10˝
GAS ORIFICE INFORMATION
ORIFICE SIZE
ORIFICE SIZE REQUIRED AT OTHER ELEVATIONS
AT SEA LEVEL
2000 ft
3000 ft
4000 ft
5000 ft
9000 ft
32
33
34
35
35
38
39
40
41
41
42
44
41
42
42
42
43
45
50
51
51
51
51
53
51
51
52
52
52
53
52
52
53
53
53
54
60
64
64
65
65
67
67
68
68
68
69
70
73
73
77
77
78
78
77
77
77
77
78
78
1.55mm
54
54
54
54
55