32
BQMS Installation Manual
052319
1.
From the CCU, connect the CCU-Module CAN Cable to CAN Port 1 as shown below.
CAN Port on BQMS
2.
Connect the other end of the CCU-Module CAN Cable to the closest Module.
3.
Connect all the remaining Modules together with the provided CAN Cables. There are 2 CAN
ports on each Module, CAN 1 and CAN 2. It does not matter which port the cables are
connected to.
Modules Connected with CAN Cables
NOTE:
Modules use CAN communication, so they do not need to be wired in any specific
order. For example, you can wire Module 1 to Module 5, and so on.