BQMS Installation Manual
052319
5.5.3.1 Module Channel Setting for 3-Cell Connection
When connecting a Module to (3) cells (applicable to 2V, 4V, 6V cells), the CH setting switches need to
be set as shown below. Be sure to reset the Module any time the channel settings are changed.
5.5.4 Cable Connection to Multiple 12V Units:
For 12V units a single module measures up to two 12V units.
1.
The Voltage Harness includes (3) wires colored
gray
,
green
, &
blue
.
2.
The Current Harness includes (2) wires colored
red
for positive & black for negative.
3.
The Temperature Harness includes up to (8) colored wires for connection to Temperature
Sensors. (The color and number of wires depends on the number of cell temperatures being
monitored.)
4.
The last wire of the Voltage Sensing Harnesses (
blue
) connects together in the same clamp
with the first wire (
gray
) of the next harness.
5.
The last wire of the Input harness (black) connects with the first wire (
red
) of the next harness.