4.4.3
Internal Logic Function
Internal Logic Parameters
You can enter the opening or closing scenario of the channel. In this function, each relay can be
switched only one time because this reaction protects the devices from infinite loop. An internal logic
function can be parameterized separately for each output. The relay of the channel doesn’t
participate to the scenario.
Relay 1…8 state
*
don’t care
off
on
To create scenario to open or close channel relay, positions of other channels of the switch actuator
are set with these parameters. The channels that doesn’t need to participate this scenario should be
left don’t care.
4.4.4
Priority Function
If the priority function is enabled, ‘Forced positioning’ communication object is visible. It hasn’t got
any parameter. This is the standard forced position working.
Bit 1
Bit 0
Function
0
0
forced positioning not active – normal control
0
1
forced positioning not active – normal control
1
0
Forced positioning active – switch off
1
1
Forced positioning active – switch on