Product Manual SW108 and SW104
EAE KNX Switch Actuator
PM R2.0
©
EAE Technology
www.eaetechnology.com
Page 14 / 22
4.4.1
Staircase Function
Staircase Function Parameters
In order to use staircase function, ‘Staircase’ should be enabled on the function window. Than
required parameters and communication objects will be visible. The staircase function can be
parameterized for each channel.
Staircase function has got a three communication object. These are “Enable staircase function”,
“Staircase lighting duration” and “Permanent ON”.
Duration of staircase lighting [min]/ [sec]
0…*
5
…240[min]
*
0
…59 [sec]
Staircase function on time is calculated by “duration of staircase lighting”. Staircase lighting time is
defined by this parameter. At the end of the on time, the relay off or active the staircase warning
functions.
Staircase retrigger
*
not retriggerable
yes retriggerable
up to staircase lighting time 2x
up to staircase lighting time 3x
up to staircase lighting time 4x
up to staircase lighting time 5x
This parameter defines whether the staircase on time can be retrigger able or not so the on time can
be extended by ‘Enable staircase function’. You can repeat retrigger function until the repeater count
reached the maximum value (2x, 3x, 4x, 5x). If the parameter selects ‘not retriggerable’, staircase on
time doesn’t extend.
Reaction to OFF telegram
*
switch off
Ignore
After this parameter selected ‘switching off’, ignored ‘Enable staircase function’ communication
object ‘disable’ command.