4.3
Channel General
Channel General Parameters
Contact type
normally closed
*
normally open
The relays of a switching output can be parameterized as normally closed or normally open. This
feature offers the possibility of inversion the switching state. Important: This state is only valid for
switch communication object. Other relay function always works normally.
Normally closed contact
Switch state = off (0)
à
relay contact closed
Switch state = on (1)
à
relay contact open
Normally open contact
Switch state = off (0)
à
relay contact open
Switch state = on (1)
à
relay contact closed
Send switch status feedback telegram
no
after change
after request
*after change or request
The switch status feedback can be used as an active or passive communication object. Active
message object, the switch status telegram is transmitted to the bus automatically when a relay state
changes. Passive status object, there is no telegram transmission after relay state changes. If you
want to learn switch status, you must read communication object. Communication object flags are
automatically set by ETS.
NOTE:
Switching state changes by manual operation are not detected.