Multiple Unit Configuration

  

When multiple units are used in the system, the following considerations are to be made by the customer: 

 

1.  Customer panel capabilities -  

The customer is required to identify the minimum change in current the panel can detect (Panel resolution). This will 
therefore determine what resistors values to pick in section 3 below.  
 

2. Topology 

 

The customer has a number of options on how to set up the system.  

 

A single unit topology is where only one unit is connected to the customer interface line, as shown in figure 6. 
 

 

A series topology is where each unit is connected to one another as shown in figure 11. 
 

 

A star topology is where each unit is connected to a central source as shown in figure 12. 
 

3.  Resistor – TB1 Current Sense Resistor (default 3.3k

)   

The customer is required to calculate the total resistance of the system, to determine the change in current when a 
fault occurs. The default customer sense resistor value is 3.3k

. Examples of calculations of resistance for steady 

mode and fault mode are shown in table 1.  
 

Panel 

Resolution 

Topology 

Resistor: 

TB1 CSR 

No. of 

Units 

Steady Mode: 

Active/Monitoring 

Fault Mode 

1 unit fault 

All units fault 

2mA Series 

3.3k

 3 

3 x 3.3k

   9.9k

 

 

0mA  

If one unit fails the 

whole system fails 

 

7mA Star 

3.3k

 3 

3.3k

 ~ 7.3mA  

3 x 7.3mA   21.9mA 

Fault unit : 

1 x 0mA   0mA 

Normal : 

2 x 7.3mA   14.6mA 

Fault unit : 

3 x 0mA   0mA 

1.5mA Series 3.3k

 4 

4 x 3.3k

   13.2k

 

 

0mA  

If one unit fails the 

whole system fails 

 

7mA Star 

3.3k

 4 

3.3k

 ~ 7.3mA  

4 x 7.3mA   29.2mA 

Fault unit : 

1 x 0mA   0mA 

Normal : 

3 x 7.3mA   21.9mA 

Fault unit : 

4 x 0mA   0mA 

Table 1  
 
Note: - Cable fault 

  Between the panel and the first unit, a cable short, increases the current (presenting a short circuit to the panel), and a cable 

cut/open reduces current (presenting an open circuit to the panel).  

  In series topology a cable short between units will short out one of the current sense resistors which results in an increase in 

the current used by the unit, and a cable cut/open reduces current (presenting an open circuit to the panel). 

  In star topology a cable short between units will short circuit the SIL 2 monitoring line hence presenting a short circuit to the 

panel, an open circuit fault on one of the units will effectively remove one of the current sense resistors reducing total effective 
resistance hence decreasing the total current seen by the panel.   

Summary of Contents for D1xB2X Series

Page 1: ...ATMOSPH RES DANGEREUSES LE PREMIER CONDUIT DE CONDUIT DOIVENT AVOIR UN RACCORD D TANCH IT RACCORD MOINS DE 18 POUCES DE L ENFERMEMENT POUR SUBS QUENT LES CONDUITES DE CONDUIT LA DISTANCE ENTRE LA SUR...

Page 2: ...used to run the equipment The power supply selected must have the necessary capacity to provide the input current to all the units Rated at 1Hz Table 1 Electrical Ratings The input current will vary a...

Page 3: ...g grub screw in the cover and then remove the glass dome cover assembly to gain access to the chamber This can be achieved by unscrewing the glass dome cover taking extreme care not to damage the thre...

Page 4: ...All DC beacons have a blocking diode fitted in their supply input lines An end of line monitoring resistor can be connected across the ve and ve terminals in the explosion proof enclosure If an end o...

Page 5: ...ement of beacon lens cover Fit the wire guard back onto the housing over the new lens cover aligning the fixing holes of the guard lens cover and housing Refit the fixings to hold into place the fixin...

Page 6: ...and provides feedback to the control panel A fault condition can be communicated via independent fault contacts or by the introduction to the monitoring circuit of an end of line resistor A SIL 2 sys...

Page 7: ...and may not be functioning correctly 13 2 Power Failure SIL 2 Failure SIL 2 Controller failure Internal function and system checking flags fault Rapid Power cycling System indicates power instability...

Page 8: ...The fault will be seen via the SIL 2 TB1 terminals as soon as the fault occurs in either Active or Standby modes As factory default when there is no fault the TB1 terminals 1 2 will be closed putting...

Page 9: ...default customer sense resistor value is 3 3k Examples of calculations of resistance for steady mode and fault mode are shown in table 1 Panel Resolution Topology Resistor TB1 CSR No of Units Steady...

Page 10: ...fault detection current Important This configuration requires the customer to set J2 header pin to be set to position B see figure 9 as the units default position is A Figure 7 Schematic of SIL 2 syst...

Page 11: ...tar topology is when each unit is connected to a central source as shown in figure 14 3 Resistor The customer is required to calculate the total resistance a system to determine the change in current...

Page 12: ...to the panel and a cable cut open reduces current presenting an open circuit to the panel In series topology a cable short between units will short out one of the current sense resistors which results...

Page 13: ...0 Sheet 13 of 8 16 3 Header Pins Settings J1 Header Pin Postion A Factory default position pins 1 2 not linked places TB1 Current sense resistor in circuit J1 Header Pin Postion B pins 1 2 linked remo...

Page 14: ...nning hour of the unit The maximum running duration is 2 500 hours 18 Synchronised Operation All D1xB2 SIL2 beacons that are connected to the same supply line will have a synchronised flash rate at on...

Page 15: ...ng for Fault Resistor and Customer EOL Resistor The customer is able to identify the resistor values chosen on purchase from the product code This is represented by the last two characters D1XB2X05DC0...

Page 16: ...ean Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH sales e2s com Tel 44 0 208 743 8880 www e2s com Fax 44 0 208 740 4200 Document No D191 00 601 IS Issue 1 20 03 2020 Sheet 16 of 8...

Page 17: ...an Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH sales e2s com Tel 44 0 208 743 8880 www e2s com Fax 44 0 208 740 4200 Document No D191 00 601 IS Issue 1 20 03 2020 Sheet 17 of 8 F...

Page 18: ...ean Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH sales e2s com Tel 44 0 208 743 8880 www e2s com Fax 44 0 208 740 4200 Document No D191 00 601 IS Issue 1 20 03 2020 Sheet 18 of 8...

Page 19: ...an Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH sales e2s com Tel 44 0 208 743 8880 www e2s com Fax 44 0 208 740 4200 Document No D191 00 601 IS Issue 1 20 03 2020 Sheet 19 of 8 F...

Reviews: