SIL Specific Unit Mounting Requirements 

 

The beacon should be mounted no closer that 2m from a 
beacon or light source of similar candela output. This is to 
ensure false light activation does not occur when the unit is 
monitoring the light pulse duration and flash failure. 

 

17) 

SIL 2 Reliability Data 

 

Reliability and Functional safety IEC/EN61508 which has been 
assessed and is considered suitable for use in low demand 
safety function: 

 

 

Random Hardware Failures and Architectural constraints 
(route 1

H

 

As an unvoted item (i.e. hardware fault tolerance of 0) at 
SIL 2 

The product was assessed against failure modes: 

 

Failure respond to an input by lighting a beacon 

 

Spurious light output despite no input 

 

Integrity

 

in

 

respect

 

of

 

failure

 

to

 

release

 

SIL

 

2

 

Total

 

Failure

 

rate

 

0.37

 

pmh

 

“hazardous”

 

failure

 

rate

 

(revealed)

 

0.297

 

pmh

 

“hazardous”

 

failure

 

rate

 

(unrevealed)

 

0.003

 

pmh

 

“safe”

 

failure

 

rate

 

(revealed)

 

0.006

 

pmh

 

“safe”

 

failure

 

rate

 

(unrevealed)

 

0

 

Diagnostic

 

Coverage

 

99%

 

System

 

type

 

B

 

Hardware

 

Fault

 

Tolerance

 

0

 

Safe

 

Failure

 

Fraction

 

>99%

 

PFD

 

(hazardous

 

failure)

 

3.8

 

x

 

10

5

 

Proof

 

Test

 

Interval

 

Up

 

to

 

1

 

year

 

 

The SIL 2 units life is dependent on the cumulative running 
hour of the unit. The maximum running duration is 2,500 hours. 

 

18) 

Synchronised Operation

 

 

All D1xB2 SIL2 beacons that are connected to the same 
supply line will have a synchronised flash rate at one flash 
every second. 

 
 
 
 
 
 
 
 
 
 
 
 
 

19) 

End of Line Monitoring 

 

On the D1xB2 SIL2 beacons, DC reverse line monitoring can 
be used if required. All DC beacons have a blocking diode 
fitted in their supply input lines. An end of line monitoring diode 
or an end of line monitoring resistor can be connected across 
the +ve and –ve terminals. 
We suggest that with the SIL system the customer selected 
EOL resistor is kept to a value of 2.2k

 however variation is 

allowed as required by the SIL systems PLC parameters. See 
section 16.2 and 21. 
Values of current draw are given for the 2.2k

 resistor if used 

as set up in section 14. 

 

If an alternative value end of line resistor is used it must have 
a minimum resistance value of 3.3k

 and a minimum wattage 

of 0.5 watts or a minimum resistance value of 500

 and a 

minimum wattage of 2 watts. 

 

20) 

SIL 2 Hard Reset 

 

If required to hard system reset the unit, firstly, the unit will 
need to be opened, to carry out this operation see section 7.  

 

Warning

: - Ensure that an explosive atmosphere is not 

present during reset operation. 

 

Power down the unit completely for a minimum of 30 seconds. 
Move the hard reset header pin (Jumper J7) to reset position 
shown. Then power the unit for a minimum of 5 seconds. 
Power down the unit for 30 seconds and then move the header 
pin back to the Normal Position.  
The unit has been reset. Close the unit as noted in section 7. 
If the hard reset does not correct the fault the unit or power 
supply integrity will need further investigation. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Summary of Contents for D1xB2X Series

Page 1: ...ATMOSPH RES DANGEREUSES LE PREMIER CONDUIT DE CONDUIT DOIVENT AVOIR UN RACCORD D TANCH IT RACCORD MOINS DE 18 POUCES DE L ENFERMEMENT POUR SUBS QUENT LES CONDUITES DE CONDUIT LA DISTANCE ENTRE LA SUR...

Page 2: ...used to run the equipment The power supply selected must have the necessary capacity to provide the input current to all the units Rated at 1Hz Table 1 Electrical Ratings The input current will vary a...

Page 3: ...g grub screw in the cover and then remove the glass dome cover assembly to gain access to the chamber This can be achieved by unscrewing the glass dome cover taking extreme care not to damage the thre...

Page 4: ...All DC beacons have a blocking diode fitted in their supply input lines An end of line monitoring resistor can be connected across the ve and ve terminals in the explosion proof enclosure If an end o...

Page 5: ...ement of beacon lens cover Fit the wire guard back onto the housing over the new lens cover aligning the fixing holes of the guard lens cover and housing Refit the fixings to hold into place the fixin...

Page 6: ...and provides feedback to the control panel A fault condition can be communicated via independent fault contacts or by the introduction to the monitoring circuit of an end of line resistor A SIL 2 sys...

Page 7: ...and may not be functioning correctly 13 2 Power Failure SIL 2 Failure SIL 2 Controller failure Internal function and system checking flags fault Rapid Power cycling System indicates power instability...

Page 8: ...The fault will be seen via the SIL 2 TB1 terminals as soon as the fault occurs in either Active or Standby modes As factory default when there is no fault the TB1 terminals 1 2 will be closed putting...

Page 9: ...default customer sense resistor value is 3 3k Examples of calculations of resistance for steady mode and fault mode are shown in table 1 Panel Resolution Topology Resistor TB1 CSR No of Units Steady...

Page 10: ...fault detection current Important This configuration requires the customer to set J2 header pin to be set to position B see figure 9 as the units default position is A Figure 7 Schematic of SIL 2 syst...

Page 11: ...tar topology is when each unit is connected to a central source as shown in figure 14 3 Resistor The customer is required to calculate the total resistance a system to determine the change in current...

Page 12: ...to the panel and a cable cut open reduces current presenting an open circuit to the panel In series topology a cable short between units will short out one of the current sense resistors which results...

Page 13: ...0 Sheet 13 of 8 16 3 Header Pins Settings J1 Header Pin Postion A Factory default position pins 1 2 not linked places TB1 Current sense resistor in circuit J1 Header Pin Postion B pins 1 2 linked remo...

Page 14: ...nning hour of the unit The maximum running duration is 2 500 hours 18 Synchronised Operation All D1xB2 SIL2 beacons that are connected to the same supply line will have a synchronised flash rate at on...

Page 15: ...ng for Fault Resistor and Customer EOL Resistor The customer is able to identify the resistor values chosen on purchase from the product code This is represented by the last two characters D1XB2X05DC0...

Page 16: ...ean Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH sales e2s com Tel 44 0 208 743 8880 www e2s com Fax 44 0 208 740 4200 Document No D191 00 601 IS Issue 1 20 03 2020 Sheet 16 of 8...

Page 17: ...an Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH sales e2s com Tel 44 0 208 743 8880 www e2s com Fax 44 0 208 740 4200 Document No D191 00 601 IS Issue 1 20 03 2020 Sheet 17 of 8 F...

Page 18: ...ean Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH sales e2s com Tel 44 0 208 743 8880 www e2s com Fax 44 0 208 740 4200 Document No D191 00 601 IS Issue 1 20 03 2020 Sheet 18 of 8...

Page 19: ...an Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH sales e2s com Tel 44 0 208 743 8880 www e2s com Fax 44 0 208 740 4200 Document No D191 00 601 IS Issue 1 20 03 2020 Sheet 19 of 8 F...

Reviews: