background image

_______________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e2s.com             Fax: +44 (0)208 740 4200 
Document No. D191-00-601-IS           Issue 1         20-03-2020                         Sheet 7 of 8

 

 

 

Standby Mode

 – This is where the power supply polarity is 

reversed so negative (–ve) is fed to the positive (+) beacon 
terminal and positive (+) is fed to the negative (–ve) beacon 
terminal. 
In this mode the beacon will not flash but the SIL 2 unit is 
monitoring power supply and is set-up ready to go to Active 
(alarm) mode. 
Power relay RLY1-1 will be open whilst SIL 2 relay RLY1-2 will 
be closed contact between terminals 1 & 2. 
If power is disrupted the SIL 2 unit will go into 

Fault mode

, in 

fault mode the Power relay RLY1-1 will close whilst SIL 2 relay 
RLY1-2 will become an open circuit between terminals 1 & 2. 

 

Active Mode

 – This is where the power is in normal polarity, 

positive (+) supplied to the positive (+) beacon terminal and 
negative (–ve) is supplied to the negative (–ve) beacon 
terminal. 
In this mode the beacon will flash giving the warning signal, 
the SIL 2 unit is actively checking the beacons function for 
flash output and beacon controller signal generation to the 
right flash frequency. 
Power relay RLY1-1 will be open whilst SIL 2 relay RLY1-2 will 
be closed contact between terminals 1 & 2. 
The SIL 2 unit will also check for signal polarity. 
If a fault is found the SIL 2 unit will go into 

Fault mode

If power is disrupted the SIL 2 unit will go into 

Fault mode

, in 

fault mode the Power relay RLY1-1 will close whilst SIL 2 relay 
RLY1-2 will become an open circuit between terminals 1 & 2. 

 

Fault modes

 - The fault modes listed 13-1 & 13-2 below will 

make the SIL 2 unit change the state of the fault relays 
In fault mode the Power relay RLY1-1 will close whilst SIL 2 
relay RLY1-2 will become open be circuit between terminals 1 
& 2. 
 

13-1 Beacon Failure 

 

 

Flash Failure – No Flash detected 

  Beacon Controller failure – No flash trigger pulse 

detected 

 

Flash Rate Failure – Regular 1 Hz flash cycle erratic 
 

Resetting Failure - It is possible that the SIL 2 unit can be reset 
by powering the unit off for a period greater than 20 seconds. 
On restarting the unit and running through the commissioning 
cycle, the fault may clear. It is necessary to run the test function 
cycle again to see if the fault is still evident. If the relays 
activate again the unit must be checked as it is showing a 
failure and may not be functioning correctly. 
 
 
 
 

13-2 Power Failure / SIL 2 Failure 

 

 

SIL 2 Controller failure – Internal function and system 
checking flags fault 

  Rapid Power cycling – System indicates power 

instability 

 Total 

Power 

Failure 

 

 
Resetting Failure - It is possible that the SIL 2 unit can be reset 
by hard resetting the unit using the reset jumper within the unit 
(see section 20) on hard resetting. 
On restarting the unit and running through the commissioning 
cycle, the fault may clear. It is necessary to run the test function 
cycle again to see if the fault is still evident. If the relays 
activate again the unit must be checked as it is currently 
showing a failure and may not be functioning correctly. 
 

Commissioning System - Functional start-up of System 
(Normally in reverse polarity mode) 

When Commissioning system the power must not be disrupted 
to the SIL 2 Unit within the unit’s initialization cycle which is 

seconds

 

Once past this period the SIL 2 system is fully operational and 
will be in monitoring the beacon and power in Standby mode. 

 

The relay RLY1-2 on the SIL 2 unit will only remain open for a 
maximum of 1 second on commissioning start-up. 
Then they will close contact 1 & 2 showing healthy operation 
and only open in the event of a fault or power down. 

 

System Testing (Active Mode normal polarity) 

The SIL 2 system will remain monitoring the power in standby 
mode until the polarity is changed to normal mode to enable 
an active system for beacon functional testing. 

 

Important

: - The polarity must be held in active mode for a 

period in excess of 

15 seconds

 to ensure a full system check 

is performed. 
Whilst the system is being checked the beacon controller and 
flash pulses are monitored and checked for correct pattern 
timing. 
Once the test period has been completed the unit can be 
switched back to standby mode by reversing the polarity. 
If no faults have been found during the test the relays will 
remain in there steady state. 
The SIL 2 unit will continue to monitor the power and mode. 

Important

: - The automated test cycle 

must

 be undertaken 

on at least a weekly basis to maintain the SIL 2 units reliability. 

 

System Activation (Active Mode normal polarity) 

The SIL 2 system will remain monitoring the power in standby 
mode until the polarity is changed to Active mode to enable an 
active system for beacon to function as a warning signaling 
device. 

 

Important

 :- The polarity must be held in active mode for a 

period in excess of 15 seconds to ensure a full system check 
is performed whilst in alarm mode, although it is expected that 
during a system activation this period will be significantly 
greater. 

Note

 :- The fault indication signal on TB1 can take up to 1.5 

seconds to indicate system fault.

 

 
 

Summary of Contents for D1xB2X Series

Page 1: ...ATMOSPH RES DANGEREUSES LE PREMIER CONDUIT DE CONDUIT DOIVENT AVOIR UN RACCORD D TANCH IT RACCORD MOINS DE 18 POUCES DE L ENFERMEMENT POUR SUBS QUENT LES CONDUITES DE CONDUIT LA DISTANCE ENTRE LA SUR...

Page 2: ...used to run the equipment The power supply selected must have the necessary capacity to provide the input current to all the units Rated at 1Hz Table 1 Electrical Ratings The input current will vary a...

Page 3: ...g grub screw in the cover and then remove the glass dome cover assembly to gain access to the chamber This can be achieved by unscrewing the glass dome cover taking extreme care not to damage the thre...

Page 4: ...All DC beacons have a blocking diode fitted in their supply input lines An end of line monitoring resistor can be connected across the ve and ve terminals in the explosion proof enclosure If an end o...

Page 5: ...ement of beacon lens cover Fit the wire guard back onto the housing over the new lens cover aligning the fixing holes of the guard lens cover and housing Refit the fixings to hold into place the fixin...

Page 6: ...and provides feedback to the control panel A fault condition can be communicated via independent fault contacts or by the introduction to the monitoring circuit of an end of line resistor A SIL 2 sys...

Page 7: ...and may not be functioning correctly 13 2 Power Failure SIL 2 Failure SIL 2 Controller failure Internal function and system checking flags fault Rapid Power cycling System indicates power instability...

Page 8: ...The fault will be seen via the SIL 2 TB1 terminals as soon as the fault occurs in either Active or Standby modes As factory default when there is no fault the TB1 terminals 1 2 will be closed putting...

Page 9: ...default customer sense resistor value is 3 3k Examples of calculations of resistance for steady mode and fault mode are shown in table 1 Panel Resolution Topology Resistor TB1 CSR No of Units Steady...

Page 10: ...fault detection current Important This configuration requires the customer to set J2 header pin to be set to position B see figure 9 as the units default position is A Figure 7 Schematic of SIL 2 syst...

Page 11: ...tar topology is when each unit is connected to a central source as shown in figure 14 3 Resistor The customer is required to calculate the total resistance a system to determine the change in current...

Page 12: ...to the panel and a cable cut open reduces current presenting an open circuit to the panel In series topology a cable short between units will short out one of the current sense resistors which results...

Page 13: ...0 Sheet 13 of 8 16 3 Header Pins Settings J1 Header Pin Postion A Factory default position pins 1 2 not linked places TB1 Current sense resistor in circuit J1 Header Pin Postion B pins 1 2 linked remo...

Page 14: ...nning hour of the unit The maximum running duration is 2 500 hours 18 Synchronised Operation All D1xB2 SIL2 beacons that are connected to the same supply line will have a synchronised flash rate at on...

Page 15: ...ng for Fault Resistor and Customer EOL Resistor The customer is able to identify the resistor values chosen on purchase from the product code This is represented by the last two characters D1XB2X05DC0...

Page 16: ...ean Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH sales e2s com Tel 44 0 208 743 8880 www e2s com Fax 44 0 208 740 4200 Document No D191 00 601 IS Issue 1 20 03 2020 Sheet 16 of 8...

Page 17: ...an Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH sales e2s com Tel 44 0 208 743 8880 www e2s com Fax 44 0 208 740 4200 Document No D191 00 601 IS Issue 1 20 03 2020 Sheet 17 of 8 F...

Page 18: ...ean Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH sales e2s com Tel 44 0 208 743 8880 www e2s com Fax 44 0 208 740 4200 Document No D191 00 601 IS Issue 1 20 03 2020 Sheet 18 of 8...

Page 19: ...an Safety Systems Ltd Impress House Mansell Road Acton London W3 7QH sales e2s com Tel 44 0 208 743 8880 www e2s com Fax 44 0 208 740 4200 Document No D191 00 601 IS Issue 1 20 03 2020 Sheet 19 of 8 F...

Reviews: