INSTRUCTION MANUAL (ATEX/IECEx/SIL2)
D1xB2X05, D1xB2X10, D1xB2X15 SIL 2 Xenon Beacons
For use in Hazardous Locations
1) Warnings
DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
DO NOT OPEN WHEN ENERGISED
POTENTIAL ELECTROSTATIC CHARGING
HAZARD - CLEAN ONLY WITH A DAMP
CLOTH
HIGH VOLTAGE SHOCK HAZARD. WAIT 5
MINUTES AFTER REMOVING POWER
BEFORE OPENING THE ENCLOSURE
DO NOT PAINT
TO REDUCE THE RISK OF IGNITION OF
HAZARDOUS ATMOSPHERES, THE FIRST
CONDUIT RUN MUST HAVE A SEALING
FITTING CONNECTED WITHIN 18 INCHES
OF ENCLOSE. SUBSEQUENT CONDUIT
RUNS MUST HAVE A SEALING FITTING
CONNECTED AS CLOSE AS PRACTICAL TO
THE WALL OF THE ENCLOSURE, BUT IN
NO CASE MORE THAN THE SIZE OF THE
CONDUIT OR 50MM, WHICHEVER IS THE
LESSER.
TO PREVENT IGNITION OF GROUP A, B, C
AND D ATMOSPHERES - SEE
INSTRUCTION FOR CHEMICAL
COMPATIBILITY
Avertissement:
NE PAS OUVRIR UN PRESENCE
D’ATMOSPHERE EXPLOSIVE
NE PAS OUVRIR ENERGIE
DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE
HAUT TENSION, RISK DE CHOC.
ATTENDEZ 5 MINUTES APRES AVOIR
DEBRANCHE L’ALIMENTATION AVANT
D’OUVRIR LA BOITIER
NE PAS PEINTURER
POUR RÉDUIRE LE RISQUE
D'INFLAMMATION DES ATMOSPHÈRES
DANGEREUSES, LE PREMIER CONDUIT DE
CONDUIT DOIVENT AVOIR UN RACCORD
D'ÉTANCHÉITÉ RACCORDÉ À MOINS DE 18
POUCES DE L'ENFERMEMENT. POUR
SUBSÉQUENT LES CONDUITES DE
CONDUIT LA DISTANCE ENTRE LA
SURFACE DE LA MASSE DE REMPLISSAGE
AU PLUS PRÈS DE L’ENVELOPPE DOIT
ÊTRE AUSSI PETITE QUE CE QUI EST
RÉALISABLE MAIS EN AUCUN CAS
SUPÉRIEURE À LA PLUS PETITE DES
DIMENSIONS CORRESPONDANT À LA
TAILLE DU CONDUIT OU À 50 MM.
POUR PRÉVENIR L'INFLAMMATION DES
ATMOSPHÈRES DES GROUPES A, B, C ET
D-VOIR L'INSTRUCTION POUR LA
COMPATIBILITÉ CHIMIQUE
2) Rating & Marking Information
2.6 ATEX / IECEx certification
The D1xB2X Xenon beacons comply with the following
standards:
EN IEC60079-0:2018 / IEC60079-0:2017 (Ed 7)
EN60079-1:2014 / IEC60079-1 (Ed. 7) (2014)
EN60079-31:2014 / IEC60079-31 (Ed. 2) (2013)
The D1xB2X05DC024 Xenon Beacons are rated as follows:
Ex db IIC T4 Gb Ta -55°C to +80°C
Ex db IIC T5 Gb Ta -55°C to +75°C
Ex db IIC T6 Gb Ta -55°C to +60°C
Ex tb IIIC T104°C Db Ta -55°C to +80°C
The D1xB2X10DC024 Xenon Beacons are rated as follows:
Ex db IIC T4 Gb Ta -55°C to +80°C
Ex db IIC T5 Gb Ta -55°C to +45°C
Ex tb IIIC T135°C Db Ta -55°C to +80°C
The D1xB2X15DC024 Xenon Beacons are rated as follows:
Ex db IIC T3 Gb Ta -55°C to +80°C
Ex db IIC T4 Gb Ta -55°C to +65°C
Ex tb IIIC T146°C Db Ta -55°C to +80°C
Certificate No.
DEMKO 19 ATEX 2009X
IECEx ULD 19.0006X
ATEX Mark, Equipment
Group and Category
:
CE Marking
Notified Body No.:
The units can be installed in locations with the following
conditions:
Area Classification:
Zone 1
Explosive gas air mixture likely to occur in
normal operation.
Zone 2
Explosive gas air mixture not likely to occur
in normal operation, and if it does, it will only
exist for a short time.
2813
II 2G
II 2D