41
7.4.4.6 Switching status of load outputs
The switching status of the output channels are sent by the SCS200 within the CAN message mentioned below.
The message will be transmitted as a response to the corresponding transmission request.
PGN 65295 – Proprietary B
Transmission Rate:
as requested by the user, max. 100 ms
Data Length:
8 bytes
Data page:
0
PDU format
255
PDU Specific:
15
Default Priority:
6
Parameter Group Number: 65295 (FF0Fh)
CAN-ID 0x18FF0Fxx
xx Node address SCS200
Overview set-up CAN data
Example
Overload at channel 2 and open load at channel 5
Node-ID SCS200: 0xA0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Contents
channels
1 & 2
channels
3 & 4
channels
5 & 6
channels
7 & 8
channels
9 & 10
channels
11 & 12
not used
not used
Unit
–
–
–
–
–
–
–
–
Byte
Bit
Description
Value
Byte 1
bits 8 – 5
Switching status channel 1
0x0…0x1
bits 4 – 1
Switching status channel 2
0x0…0x1
Byte 2
bits 8 – 5
Switching status channel 3
0x0…0x1
bits 4 – 1
Switching status channel 4
0x0…0x1
Byte 3
bits 8 – 5
Switching status channel 5
0x0…0x1
bits 4 – 1
Switching status channel 6
0x0…0x1
Byte 4
bits 8 – 5
Switching status channel 7
0x0…0x1
bits 4 – 1
Switching status channel 8
0x0…0x1
Byte 5
bits 8 – 5
Switching status channel 9
0x0…0x1
bits 4 – 1
Switching status channel 10
0x0…0x1
Byte 6
bits 8 – 5
Switching status channel 11
0x0…0x1
bits 4 – 1
Switching status channel 12
0x0…0x1
CAN data
CAN-ID
CAN data
0x18FF0EA0
0x01 0x00 0x20 0x00 0x00 0x00 0x00 0x00