51
Table 8
Fault/Error and error code
Cause
Solution
Failure BCC during
installation
39
- If there is a failure during
the installation of the BCC.
- Consult qualified service.
BCC activation
50
- BCC activation procedure is
not completed.
- Consult qualified service.
BCC copy
52
- BCC activation procedure is
not completed.
- Consult qualified service.
System error
99
- Defective electronic board. - Consult qualified service.
4
4
If the temperature at the boiler
sensor (Flow temperature) falls
below 1°C, all actuators will be
stopped.
Frost Protection
- CH NTC’s temperature is
below 0°C.