UPR700 Microprocessor-Based Pressure/Process Indicator
63
LOGIC INPUT CONFIGURATION - Group 4
Available:
Always.
Upper display: Configuration of logic input.
Lower display: LI.TYP
Range:
OFF, AL, P, AL-P, CAL.0, ALL. Disabled, alarm reset, peak reset, alarm and peak
reset, zero calibration, alarm, peak reset, zero cal/all
Default value:
Alarm and peak reset.
LOGIC INPUT STATUS - Group 4
Available:
Only if LI.TYP is different than OFF.
Upper display: Status of logic input.
Lower display: LI.STS
Range:
CLOSE, OPEn. The logic input is considered active when the contact is closed or
open with respect to this parameter.
Default value:
Closed.
PEAK DETECTION - Group 4
Available:
Always.
Upper display: Polarity of peak detector.
Lower display: PEAK
Range:
OFF, HI, LO. Disabled, maximum peak, minimum peak.
Default value:
Maximum peak.
LINE FREQUENCY - Group 4
Available:
Always.
Upper display: Line frequency rejection.
Lower display: LINE.F
Range:
50, 60. 50 Hz, 60 Hz.
Default value:
60.
LOADING DEFAULT DATA - Group 4
Available:
Only if access to level C is allowed.
Upper display: OFF
Lower display: DEFLT
Range:
Use
▼
▲
keys to switch the upper display from OFF to On 4, then press FUNC key
to load the default data of the parameters belonging to group 1, group 2, group 3
and group 4.