62
Range:
From 0.1 to 10.0% of the selected range.
Default value:
1.0%
ALARM 2 RESET MODE - Group 4
Available:
Only if A2.LNK is different than OFF.
Upper display: Selected reset mode for alarm 2.
Lower display: A2.RES
Range:
Auto, LAtCh. Automatic reset, manual reset
Default value:
Auto.
ALARM 2 FAILSAFE MODE - Group 4
Available:
Only if A2.LNK is different than OFF.
Upper display: Selected failsafe mode for alarm 1.
Lower display: A2.FSM
Range:
FS, nFS. Failsafe mode, non-failsafe mode.
Default value:
Failsafe mode.
ALARM 3 HYSTERESIS - Group 4
Available:
Only if A3.LNK is different than OFF.
Upper display: Alarm 3 hysteresis
Lower display: A3.HYS
Range:
From 0.1 to 10.0% of the selected range.
Default value:
1.0%
ALARM 3 RESET MODE - Group 4
Available:
Only if A3.LNK is different than OFF.
Upper display: Selected reset mode for alarm 3.
Lower display: A3.RES
Range:
Auto, LAtCh. Automatic reset, manual reset.
Default value:
Auto.
ALARM 3 FAILSAFE MODE - Group 4
Available:
Only if A3.LNK is different than OFF.
Upper display: Selected failsafe mode for alarm 1.
Lower display: A3.FSM
Range:
FS, nFS. Failsafe mode, non-failsafe mode.
Default value:
Failsafe mode.