38
8.7.1 S
ETTING
THE
M
AIN
A
NALOG
O
UTPUT
T
YPE
The Main Analog Output Type sets the output to specific voltages or currents. The available outputs
are 0-20 mA, 4-20 mA, 0-10 VDC, -10 to +10 VDC, and 0-5 VDC. To change or view this value,
press the
FUNC
key until
nonE
and
GROUP
show on the display. Press the
▲
key until
5
shows in
the upper display. Press the
FUNC
key until the lower display changes to
MO.TYP
, and the upper
display shows the selected type. Press the
▼
or
▲
keys until the upper display changes to the
desired value. Then press the
FUNC
key to lock in the value and advance to the next parameter, or
press
RESET
to return to the operating screen. Similarly if the unit has a Secondary input, the
Secondary Analog Output Type
(SO.TYP)
can be set in the same manner.
Remember to change the jumper settings to correspond to the proper output as shown in Fig. 9 for
board location and Fig. 11 for Main Analog output jumpers and Fig. 12 for Second Analog output
jumpers.
8.7.2 S
ETTING
THE
M
AIN
A
NALOG
O
UTPUT
L
INK
To change or view this value, press the
FUNC
key until
nonE
and
GROUP
show on the display.
Press the
▲
key until
3
shows in the upper display. Press the
FUNC
key until the lower display
changes to
MO.LNK
, and the upper display shows the selected type, either
PrI.In
(the primary input)
or
SEc.In
(the secondary Input). Press the
▼
or
▲
keys until the upper display changes to the desired
value. Then press the
FUNC
key to lock in the value and advance to the next parameter, or press
RESET
to return to the operating screen. . Similarly the Secondary Analog Output Link
(SO.LNK)
can be set in the same manner.
8.7.3 S
ETTING
THE
M
AIN
A
NALOG
O
UTPUT
R
ANGE
L
OW
To change or view the Main Analog Output Range Low, press the
FUNC
key until
nonE
and
GROUP
show on the display. Press the
▲
key until
3
shows in the upper display. Press the
FUNC
key until the lower display changes to
MO.LO
. Press the
▼
or
▲
keys until the upper display
changes to the desired value. The value may be anything from 0 to the primary input full scale value,
PI.FSV
if the
MO.LNK
is set to
PrL.Ln
, or if the
MO.LNK
is set to
SEc.Ln
, the value may be from -
1000 to 3000. Once the desired value is set, press the
FUNC
key to lock in the value and advance
to the next parameter, or press
RESET
to return to the operating screen. Similarly the Secondary
Analog Output Range Low
(SO.LO)
can be set in the same manner.
8.7.4 S
ETTING
THE
M
AIN
A
NALOG
O
UTPUT
R
ANGE
H
IGH
To change or view the Main Analog Output Range High, press the
FUNC
key until
nonE
and
GROUP
show on the display. Press the
▲
key until
3
shows in the upper display. Press the
FUNC
key until the lower display changes to
MO.HI
. Press the
▼
or
▲
keys until the upper display
changes to the desired value. The value may be anything from 0 to the primary input full scale value,
PI.FSV
if the
MO.LNK
is set to
PrL.Ln
, or if the
MO.LNK
is set to
SEc.Ln
, the value may be from -
1000 to 3000. Once the desired value is set, press the
FUNC
key to lock in the value and advance
to the next parameter, or press
RESET
to return to the operating screen. Similarly the Secondary
Analog Output Range High
(SO.HI)
can be set in the same manner.
Summary of Contents for UPR700
Page 14: ...14 Fig 2 Model UPR700 Outline Drawing...
Page 16: ...16 Fig 3 UPR700 Wiring 4 20mATransmitter Internal 24VDC Power Supply Primary Input...
Page 67: ...NOTES...
Page 68: ...NOTES...
Page 70: ...DYNISCO LLC 38 FORGE PARKWAY FRANKLIN MA 02038 ATTN MARKETING DEPT Place Stamp Here...
Page 71: ......