23
Maintenance personnel should check the equipment according to the prompt information,
determine the type and location of the fault, and take appropriate measures to ensure the
system in the best working condition, so as not to affect the system output.
This phenomena and measures are shown in table 4-2
Table 4-2 minor alarm
Alert category
Alarm indication
Countermeasure
Low total voltage
alarm
System working status and
yellow light is always on
Discharge at reduced power
and charging in time
Low cell voltage
alarm
System working status and
yellow light is always on
Discharge at reduced power
and charging in time
4.3 Analysis and treatment of common faults
Analysis and treatment of common faults in the Table 4-3:
Table 4-3 Analysis and treatment of common faults
Item
Fault phenomenon
Reason analysis
Solution
1
The indicator does not
respond after the power
on
Power switch is
broken
Check the power switch
2
No DC output
Battery data status
is abnormal
The network management
is connected to backstage
supporter server to read
the battery information.
3
The DC power supply time
is too short
Battery capacity
become smaller
Storage battery
replacement
4
The battery can't be full of
electricity
Charging voltage is
too low
Adjust charging voltage
within 54V ~ 55V range
5
The power line sparks once
power on and ALM light
RED
Power connection
short-circuit
Turn off the battery, check
the cause of the short
circuit
If you have any technical help or question, please contact the seller in time.