22
SECTION 6
–
KEYPAD
•
The EC 2000 can be either controlled via the keypad or from external pilot device, but initial
programming must be done with the keypad.
•
The keypad is plugged into the “PL2
-
KEYPAD” male pin header on 15
-1200-1.
•
Dynamatic® part number: 037-000544-0100 (Keypad with 10ft cable)
o
Other cable sizes available upon request
Table 4: Keypad Button Descriptions
Key
Function
Notes
P1
Preset 1
Set in Menu L, “Process”
P2
Preset 2
Set in Menu L, “Process”
P3
Preset 3
Set in Menu L, “Process”
P4
Preset 4
Set in Menu L, “Process”
ENTER
Allows user into a menu or submenu; confirms value
change
EXIT
Allows user to back out of a menu or submenu.
SELECT
METER
User changes displayed meters (Meter 1 or Meter 2) on
bottom two lines of the keypad.
Meter options include: Reference, Motor Amps,
Clutch Amps, Brake Amps, Feedback, and Drive
Speed.
F1/F2/F3
Successive pushing locks or unlocks the keypad
“Locked” does not allow changing of parameters
↑
Allows user to cycle through menus or values in
ascending order
→
Shift
Allows user to change between individual digits
↓
Allows user to cycle through menus or values in
descending order
SET-
POINT
Reference point for speed or torque control
SPEED
TORQUE
Switches between speed or torque control
JOG
Momentary run function at a preset reference
MAN
AUTO
Switches between
“Manual” and “Automatic” mode
“Manual” refers to the use of a potentiometer for
speed/torque reference, while “Automatic” refers
to the use of a follower input such as 0-10V or 4-
20mA .
LOCAL
REMOTE
Switches between “Local” and “Remote” mode
“Local” mode is for operation from the keypad,
while “Remote” mode is for operation from
external pilot devices. Only available to toggle if
enabled in Menu A, Parameter 12.
RUN
Starts the control
Will only work in “Local” mode
STOP
Stops the control
The control can either be programmed to stop
the control via the keypad or external push
button (See Menu K).
Summary of Contents for EC 2000
Page 6: ...6 Figure 2 EC 2000 Keypad Display ...
Page 12: ...12 SECTION 5 INSTALLATION Figure 3 Standard Panel Dimensions Not to scale ...
Page 13: ...13 Figure 4 Keypad Cutout Template to Scale Inches ...
Page 14: ...14 Figure 5 Keypad Dimensions to Scale ...
Page 17: ...17 Figure 8 Start Stop Jog E STOP Wiring Figure 9 Setpoint Reference Manual Auto Mode Wiring ...
Page 19: ...19 Figure 13 Speed Pickup Wiring Figure 12 Preset Speeds PLC Run Wiring ...