31
7.6
Menu F: ANALOG OUTPUTS
The EC 2000 can output two different analog values based on a variety of statuses or
setpoints. Note that for a 4-20mA or 8-40mA output, proper programming and a 500 Ohm
resistor should be connected (See Figure 10).
1.
ANALOG 1 SELECT
Select which status, range, or setpoint will have an analog output. For example, selecting
DRIVE SPD will output an analog range (0-10V, 0-5V, 4-20mA, 8-40mA) based on the drive
speed of the unit. For example, if you have set the control to output a 0-10V signal, your
maximum speed setting is 1600 RPM, and your drive is running at 800 RPM, you will see an
output of 5V. The same options are available for ANALOG 2 SELECT.
•
DRIVE SPD
•
REFERENCE
•
SETPOINT
•
MTR AMPS
•
CLUT AMPS
•
BRAK AMPS
•
FEEDBACK
•
NONE
2.
ANA 1 MIN SIGNAL
If desiring to output a 4-20mA signal, set this value to 20% (20% of 20 is 4).
3.
ANA 1 MAX SIGNAL
4.
ANA 1 MIN OUTPUT
5.
ANA 1 MAX OUTPUT
6.
ANALOG 2 SELECT
7.
ANA 2 MIN SIGNAL
8.
ANA 2 MAX SIGNAL
9.
ANA 2 MIN OUTPUT
10.
ANA 2 MAX OUTPT