1
2
3
4
COIL RESISTANCE CHECK
REMOVE THE
MAGNET COIL
CONNECTOR
FROM THE
CIRCUIT BOARD TO
PERFORM THE COIL TEST
PROPER COIL RESISTANCE SHOULD BE
FROM POINTS 1 TO 3, ~ 53 OHMS
FROM POINTS 2 TO 4, ~ 53 OHMS
ELECTRICAL SPECIFICATIONS
OPERATING VOLTAGES
12 OR 24 VAC / VDC
CURRENT CONSUMPTION, ALL MODELS
12 VAC / VDC - 0.44 A
24 VAC / VDC - 0.22 A
Notes:
1.
This lock may accept any one of 4 different input voltages and be furnished
with a combination of options. Refer to page 1 for option location and
pages 2 and 3, fi gure A thru E, for wiring instructions that apply to
your
specifi c installation.
2.
For additional system wiring information, refer to the installation
documentation furnished with the external hardware and / or
peripheral devices (I.E. power supply, station controls, keypad, card
readers, etc.) supplied by DynaLock and / or others.
3000 / 2000 TD OPTION
(TIME DELAY)
12 / 24
VAC / VDC
INPUT
NORMALLY CLOSED STATION CONTROL(S),
I.E. PUSHBUTTONS, KEYSWITCHES, ETC.
WIRE MULTIPLE CONTROLS IN SERIES AS
SHOWN.
FIG. E
TIME DELAY OPERATION
1.
PUT A JUMPER ACROSS TERMINALS 3 & 4.
2.
MOMENTARILY OPENING THE CONTACT(S) AND
INTERRUPTING THE POWER ON 1 & 2 UNLOCKS THE DOOR.
THE DOOR WILL RELOCK AFTER THE DURATION OF THE TD.
3.
SEE PAGE ONE FOR THE LOCATION OF THE TIMER
ADJUSTMENT
CONTROL.
4.
TIME ADJUSTMENT RANGE IS ONE (1) TO EIGHTY (80) SECONDS.
3
ADD
JUMPER
1
2 3 4 5 6 7 8 9 10