Operating Instructions SWTD-1000
DYNALCO
16
//
8.5.5 Relay Parameter and Selection of Parameter Set
(Configuration
Æ
Relay control)
Parameter set A / B selection
As standard parameter set B may be activated via the binary input <Binary input B1>.
If parameter set B is to be deactivated, this setting should be none (always control A)
Delay time when switching A <- B
This value determines the delay from switching the binary input to the switching from parameter set B to
parameter set A.
Relay assignment with control A
Defines the relay behavior in parameter set A.
Relay assignment with control B
Defines the relay behavior in parameter set B.
Relay
Defines the source information for relay switching.
Status register
Relay dependency
•
Alarm
(Common) Alarm
(8.5.1 System Parameters (Configuration
Æ
System))
•
Sensormonitor Sensor status
(8.5.2 Sensor Parameter (Configuration
Æ
Sensor))
•
Limit
1/2
Selection of Limit 1/2
(8.5.4 Limit (Configuration
Æ
Limit))
•
Window
ExOR combination of both limits
•
On
The relay is on
•
Off
The relay is always off
Acknowledge
Acknowledge establishes if and under what conditions the relay status is held. A relay that is held no
longer reacts to the assigned signal and can only be reset via the binary input.