7. Hardware Configuration
7.1 Analog Sensor Input (Sign)
Jumper position
J1: Sensor type
J2: Adaptive trigger level range
2 wire sensors
(with 820Ohm Pull Up resistance)
28mV to 6.5V
(>20mV
rms
)
3 wire and electromagnetic sensors
(factory setting)
250mV to 6.5V
(>500mVpp)
[factory setting]
7.2 Digital Sensor Input (IQ)
No hardware configuration possible or necessary.
J2