48
Channel 22 Input Settings
P a r a m e t e r
F u n c t i o n D e s c r i p t i o n
V a l i d I n p u t s
110.22=
Channel name for CH22
Default=” “
(blank=CH22)
11 characters (including spaces)
111.22=
Units of measure for CH22
0= deg F (default)
1= deg C
2= PSI
3= PSA
4= KPA
5= FTP
6= RPM
7= “ “ (blank)
8001.22=
Input type for CH22
0= J-TC (default)
1= K-TC
2= Nickel RTD
3= Platinum RTD
4= 4-20 mA (ext. resistor req’d)
5= 0-5 V
8000.22=
Enables CH22 for scanning
0= disabled (default)
1= enabled
8017.22=
Filter speed for CH22
Minimum=0.00 (none)
Default=0.05 (slow)
Maximum=1.00 (fast)
8012.22=
Output value for 0 V or 4 mA input
Minimum=-999.0
8013.22=
Output value for 5 V or 20 mA input
Default=
0.0
Maximum=9999.0
(in channel units)
8015.22=
Inverted resistance for 4-20mA source on CH22
Minimum=0.0 1/kohms
Default=10.0 1/kohms
Maximum=100.0 1 /kohms
8008.22=
CH22 output offset to add to computed output value
Minimum=-1000.0
Default= 0.0
Maximum= 1000.0
(in channel units)
63000.22=
Shutdown trip class for CH22
0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under
63001.22=
Shutdown threshold value for CH22
Numeric value
63002.22=
Shutdown threshold hystersis for CH22
(channel units)
63003.22=
Delay time between exceeded CH22 shutdown threshold and
CH22shutdown
seconds
63000.46=
Alarm trip class for CH22
0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under
63001.46=
Alarm threshold value for CH22
Numeric value
63002.46=
Alarm threshold hysteresis for CH22
(channel units)
63003.46=
Delay time between exceeded CH22 alarm threshold and
CH22 alarm
seconds