28
Channel 2 Input Settings
P a r a m e t e r
F u n c t i o n D e s c r i p t i o n
V a l i d I n p u t s
110.2=
Channel name for CH02
Default=” “
(blank=CH02)
11 characters (including spaces)
111.2=
Units of measure for CH02
0= deg F (default)
1= deg C
2= PSI
3= PSA
4= KPA
5= FTP
6= RPM
7= “ “ (blank)
8001.2=
Input type for CH02
0= J-TC (default)
1= K-TC
2= Nickel RTD
3= Platinum RTD
4= 4-20 mA (DIP 2 switch on)
5= 0-5 V
8000.2=
Enables CH02 for scanning
0= disabled (default)
1= enabled
8017.2=
Filter speed for CH02
Minimum=0.00 (none)
Default=0.05 (slow)
Maximum=1.00 (fast)
8012.2=
Display value for 0 V or 4 mA input
Minimum=-999.0
8013.2=
Display value for 5 V or 20 mA input
Default=
0.0
Maximum=9999.0
(in channel units)
8015.2=
Inverted resistance for 4-20mA source on CH02
Minimum=0.0 1/kohms
Default=10.0 1/kohms
Maximum=100.0 1 /kohms
8008.2=
CH02 output offset to add to computed output value
Minimum=-1000.0
Default= 0.0
Maximum= 1000.0
(in channel units)
63000.2=
Shutdown trip class for CH02
0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under
63001.2=
Shutdown threshold value for CH02
Numeric value
63002.2=
Shutdown threshold hystersis for CH02
(channel units)
63003.2=
Delay time between exceeded CH02 shutdown threshold and
CH02 shutdown
seconds
63000.26=
Alarm trip class for CH02
0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under
63001.26=
Alarm threshold value for CH02
Numeric value
63002.26=
Alarm threshold hysteresis for CH02
(channel units)
63003.26=
Delay time between exceeded CH02 alarm threshold and
CH02 alarm
seconds