31
Appendix C
Channel 5 Input Settings
P a r a m e t e r
F u n c t i o n D e s c r i p t i o n
V a l i d I n p u t s
110.5=
Channel name for CH05
Default=” “
(blank=CH05)
11 characters (including spaces)
111.5=
Units of measure for CH05
0= deg F (default)
1= deg C
2= PSI
3= PSA
4= KPA
5= FTP
6= RPM
7= “ “ (blank)
8001.5=
Input type for CH05
0= J-TC (default)
1= K-TC
2= Nickel RTD
3= Platinum RTD
4= 4-20 mA (DIP 5 switch on)
5= 0-5 V
8000.5=
Enables CH05 for scanning
0= disabled (default)
1= enabled
8017.5=
Filter speed for CH05
Minimum=0.00 (none)
Default=0.05 (slow)
Maximum=1.00 (fast)
8012.5=
Display value for 0 V or 4 mA input
Minimum=-999.0
8013.5=
Display value for 5 V or 20 mA input
Default=
0.0
Maximum=9999.0
(in channel units)
8015.5=
Inverted resistance for 4-20mA source on CH05
Minimum=0.0 1/kohms
Default=10.0 1/kohms
Maximum=100.0 1 /kohms
8008.5=
CH05 output offset to add to computed output value
Minimum=-1000.0
Default= 0.0
Maximum= 1000.0
(in channel units)
63000.5=
Shutdown trip class for CH05
0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under
63001.5=
Shutdown threshold value for CH05
Numeric value
63002.5=
Shutdown threshold hystersis for CH05
(channel units)
63003.5=
Delay time between exceeded CH05 shutdown threshold and
CH05 shutdown
seconds
63000.29=
Alarm trip class for CH05
0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under
63001.29=
Alarm threshold value for CH05
Numeric value
63002.29=
Alarm threshold hysteresis for CH05
(channel units)
63003.29=
Delay time between exceeded CH05 alarm threshold and
CH05 alarm
seconds