Appendix C
Channel 9 Input Settings
P a r a m e t e r
F u n c t i o n D e s c r i p t i o n
V a l i d I n p u t s
110.9=
Channel name for CH09
Default=” “
(blank=CH09)
11 characters (including spaces)
111.9=
Units of measure for CH09
0= deg F (default)
1= deg C
2= PSI
3= PSA
4= KPA
5= FTP
6= RPM
7= “ “ (blank)
8001.9=
Input type for CH09
0= J-TC (default)
1= K-TC
2= Nickel RTD
3= Platinum RTD
4= 4-20 mA (ext. resistor req’d)
5= 0-5 V
8000.9=
Enables CH09 for scanning
0= disabled (default)
1= enabled
8017.9=
Filter speed for CH09
Minimum=0.00 (none)
Default=0.05 (slow)
Maximum=1.00 (fast)
8012.9=
Display value for 0 V or 4 mA input
Minimum=-999.0
8013.9=
Display value for 5 V or 20 mA input
Default=
0.0
Maximum=9999.0
(in channel units)
8015.9=
Inverted resistance for 4-20mA source on CH09
Minimum=0.0 1/kohms
Default=10.0 1/kohms
Maximum=100.0 1 /kohms
8008.9=
CH09 output offset to add to computed output value
Minimum=-1000.0
Default= 0.0
Maximum= 1000.0
(in channel units)
63000.9=
Shutdown trip class for CH09
0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under
63001.9=
Shutdown threshold value for CH09
Numeric value
63002.9=
Shutdown threshold hystersis for CH09
(channel units)
63003.9=
Delay time between exceeded CH09 shutdown threshold and
CH09 shutdown
seconds
63000.33=
Alarm trip class for CH09
0= Off
1= Class A over (default)
2= Class B over
3= Class C over
4= Class A under
5= Class B under
6= Class C under
63001.33=
Alarm threshold value for CH09
Numeric value
63002.33=
Alarm threshold hysteresis for CH09
(channel units)
63003.33=
Delay time between exceeded CH09 alarm threshold and
CH09 alarm
seconds