42
Sequence Nummer
Title
Priority
Stopp trigger
S 32
”Ansage”
80
D3 Low >00,1
Step Command Parameter
Announcement via recording input DMM 4650 as long as the
1:
Out
D3 set
key is being pressed (System input -20 dB).
2:
Sum=
-20 dB
Description: Closing the signaling contact (D3 = announcement
3:
DMM=
-3dB
running) switches the audio controls of the sum input to -20 dB
4:
Start
Ann.
and the controls of the announcement to -3dB. After the correct level
5:
wt
Stop
was set once in the operation menu (announcement), the
6:
End
announcement is made via one of the DMM 4650’s recording inputs.
When the message has ended the DMM 4650 returns to the stand-by
mode.
Sequence Nummer
Title
Priority
Stopp trigger
S 33
”BZB-ABC”
95
off
Step Command Parameter
BZB ABC alarm
1:
Out
A1 set
2:
wt
In A1 High
Description: Turns the sound reinforcement system’s power on
3:
Out
B4 clr
(relay Al) and waits for acknowledgment (input Al = system
4:
Out
B2 set
ready). When the system is ready, the output B4 (music program
5:
Out
B3 set
off) is opened and B2, B3 (mandatory reception E, D) is closed.
6:
Out
A3 set
Closing the signaling contact (A3 = alarm signal running) swit-
7.
Sum=
Off
ches the audio controls to the alarm signal’s priority. The signal
8:
DMM=
-5dB
sequence is defined as follows: 1 minute siren interrupted by two
9:
Count=
0003
breaks (=5 * 12sec, siren = 330 - 420 Hz), break 30 seconds and
10:
Start
A27
repeating of the signal sequence (total duration 150 sec.); the
11:
wt
Audio
utilized alarm preset is A 27 = 12 sec. siren. Afterwards the DMM
12:
Dly=
012,0s
4650 returns to the stand-by mode.
13:
wt
Delay
14:
if
Count
15:
Jump
17
16:
Jump
10
17:.
Dly=
006,0s
18:
wt
Delay
19:
Count=
0003
20:
Dly=
012,0s
21:
wt
Delay
22:
Stert
A 27
23:
wt
Audio
24:
if
Count
25:
End
26:
Jomp
20
27: